Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output type | Relays |
| Number of digital outputs | 4 |
| Rated supply voltage | 24 V DC |
| Permissible supply-voltage range | 19.2 V to 28.8 V DC |
| Maximum current per channel | 5 A |
| Rated switching voltage, DC | 24 V DC to 120 V DC |
| Rated switching voltage, AC | 24 V AC to 230 V AC |
| Suitable BaseUnits | BU type B0, B1 |
Applications
- Relay output switching: Switching digital loads through 4 normally open relay outputs with resistive or inductive loads.
Key Features
- Relay output channels: 4 normally open relay outputs with parameterizable digital outputs; current-sinking and current-sourcing operation are supported.
- Supply and current: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Current consumption is max. 100 mA without load.
- Contact switching capacity: Contact switching current is max. 5 A with resistive load and max. 2 A with inductive load. Rated switching voltage is 24 V DC to 120 V DC or 24 V AC to 230 V AC.
- Diagnostics and status: Module diagnostics, diagnostic alarms, supply-voltage monitoring, substitute values, group error, green PWR and channel-status LEDs, and green/red DIAG LED are supported.
- BaseUnit and installation: Suitable BaseUnits are BU type B0 and B1. Use BU type B1 for 2-wire connection and BU type B0 for 3-wire connection.
- Electrical isolation: The channels are electrically isolated from each other, the backplane bus, and the electronics power supply. Permissible potential difference is 240 V AC.
Frequently Asked Questions
1. How many relay outputs does 6ES7132-6MD00-0BB1 have?
It has 4 normally open relay outputs.
2. What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. What switching voltage ranges are supported?
The rated switching voltage is 24 V DC to 120 V DC or 24 V AC to 230 V AC.
4. Which BaseUnit is required for this module?
The module is suitable for BU type B0 or B1. BU type B1 is used for 2-wire connection and BU type B0 for 3-wire connection.