Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIMATIC ET 200SP relay module |
| Digital outputs | 3 |
| Relay contacts | 3; changeover contact, non-floating |
| Rated supply | 24 V DC |
| Supply range | 19.2 V DC to 28.8 V DC |
| Rated switching voltage | 24 V DC to 120 V DC; 24 V AC to 230 V AC |
| Switching capacity | 5 A with resistive load; 2 A with inductive load |
| BaseUnit | BU type U0 |
| Protection | Reverse polarity protection; external protection with miniature fuse max. 6.3 A |
| Diagnostics | Module diagnostics, diagnostic alarm, supply-voltage monitoring |
Applications
- Substitute value output: The module supports connectable substitute values for its digital relay outputs.
- Relay load switching: The relay outputs switch resistive and inductive loads within the stated switching capacities.
Key Features
- Relay outputs: 3 digital relay outputs with non-isolated changeover contacts; current-sinking and current-sourcing operation are supported.
- Switching capacity: Maximum switching capacity is 5 A with resistive load and 2 A with inductive load.
- Rated switching voltage: Rated switching voltage is 24 V DC to 120 V DC or 24 V AC to 230 V AC.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V DC to 28.8 V DC and reverse polarity protection.
- Diagnostics and interfaces: The module supports module diagnostics, diagnostic alarms, supply-voltage monitoring, PROFINET GSDML V2.45, and PROFIBUS GSD Revision 3 and 5 and higher.
Frequently Asked Questions
1. How many relay outputs does 6ES7132-6HC70-0BU0 have?
It has 3 digital relay outputs with non-isolated changeover contacts.
2. What switching voltage does the relay module support?
The rated switching voltage is 24 V DC to 120 V DC or 24 V AC to 230 V AC.
3. What BaseUnit is used for this module?
The supported BaseUnit is BU type U0 for 2-wire and 3-wire connections.