Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | DQ 16x24VDC/0.5A BA |
| Digital outputs | 16 source outputs (PNP, current-sourcing) |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V |
| Rated output current | 0.5 A per channel |
| Total module current | 8 A maximum |
| Switching capacity | 0.5 A maximum with resistive load; 5 W maximum on lamp load |
| Switching frequency | 100 Hz maximum with resistive load; 2 Hz maximum with inductive load; 10 Hz maximum on lamp load |
| BaseUnit | BU type A0 |
| Diagnostics | Module diagnostics, diagnostic alarm, supply-voltage monitoring, and group error |
| Output delay | 80 μs typical from "0" to "1" and 100 μs typical from "1" to "0" at rated load |
| Protection | Short-circuit protection and reverse polarity protection |
| Isolation | Channels not isolated from each other; isolated from backplane bus, tested with 707 V DC |
Applications
- Digital output control: Controls 24 VDC digital signals through source outputs.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
- Digital input control: Can control a digital input.
Key Features
- 16 digital outputs: Provides 16 parameterizable source outputs (PNP, current-sourcing) for 24 VDC signals.
- Output capacity: Rated output current is 0.5 A per channel; total current is limited to 8 A per module.
- Output protection: Includes short-circuit protection and reverse polarity protection for the 24 V supply.
- Diagnostics and status: Provides module diagnostics, diagnostic alarms, supply-voltage monitoring, group error, a green PWR LED, a green channel-status LED, and a green/red DIAG LED.
- BaseUnit and connection: Uses BU type A0 for 1-wire connection; 2-wire, 3-wire, and 4-wire connections require BU type A0 plus a Potential distributor module.
- Timing and isolation: Typical output delays are 80 μs from "0" to "1" and 100 μs from "1" to "0" at rated load. The channels are not isolated from each other but are isolated from the backplane bus with 707 V DC type-test isolation.
Frequently Asked Questions
1. How many digital outputs does Siemens 6ES7132-6BH00-0AA0 provide?
It provides 16 parameterizable source outputs (PNP, current-sourcing).
2. What supply and output current does the module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Rated output current is 0.5 A per channel, and total module current is limited to 8 A.
3. Which BaseUnit connections are supported?
BU type A0 is used for 1-wire connection. 2-wire, 3-wire, and 4-wire connections require BU type A0 plus a Potential distributor module.
4. What diagnostics are available?
The module provides module diagnostics, diagnostic alarms, supply-voltage monitoring, group error, a green PWR LED, a green channel-status LED, and a green/red DIAG LED.