Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIMATIC ET 200eco PN digital I/O module |
| Digital channels | 16 inputs and 16 outputs; parameterizable as DIQ |
| Input signal | 24 V DC; signal 0: -3 to +5 V; signal 1: +11 to +30 V |
| Output capacity | 0.5 A / 2 A |
| Load voltage | 24 V DC rated; permissible range 20.4 V to 28.8 V |
| PROFINET interface | 1 interface; 100 Mbit/s full duplex; 2 4-pin D-coded M12 ports |
| Protocols | PROFINET IO, EtherNet/IP, Modbus TCP, Open IE communication |
| Protection | IP65/67/69K |
Applications
- Digital signal acquisition: Acquires digital signals through parameterizable 24 V DC inputs with IEC 61131 type 3 input characteristics.
- Digital output control: Controls digital loads through current-sourcing outputs with 0.5 A / 2 A switching capacity.
- Industrial Ethernet communication: Exchanges I/O data through PROFINET IO, EtherNet/IP, or Modbus TCP interfaces.
- Channel diagnostics: Detects wire breaks, output short circuits, encoder-supply short circuits, and supply-voltage conditions.
Key Features
- 16 parameterizable DIQ channels: Provides 16 digital inputs and 16 digital outputs, parameterizable as DIQ, in groups of 8.
- 24 V DC signal supply: Input rated value is 24 V DC; signal 0 is -3 to +5 V and signal 1 is +11 to +30 V.
- 0.5 A / 2 A outputs: Digital outputs support 0.5 A / 2 A switching capacity and have electronic short-circuit protection per channel.
- PROFINET and Ethernet interfaces: Provides 1 PROFINET interface with 100 Mbit/s full duplex, 2 4-pin D-coded M12 ports, and an integrated switch.
- Multi-protocol communication: Supports PROFINET IO, EtherNet/IP, Modbus TCP, Open IE communication, MRP, and S2 system redundancy.
- Channel and supply diagnostics: Provides wire-break, output short-circuit, encoder-supply short-circuit, supply-voltage monitoring, and configurable diagnostic alarms.
Frequently Asked Questions
1. How many I/O channels does 6ES7143-6BH00-0BB0 provide?
It provides 16 digital inputs and 16 digital outputs, parameterizable as DIQ, in groups of 8.
2. What input signals does the module support?
The input rated value is 24 V DC. Signal 0 is -3 to +5 V, and signal 1 is +11 to +30 V.
3. What communication interfaces and protocols are supported?
It has 1 PROFINET interface with 100 Mbit/s full duplex, 2 4-pin D-coded M12 ports, and an integrated switch. It supports PROFINET IO, EtherNet/IP, and Modbus TCP.
4. What diagnostics are available?
Diagnostics include wire break, output short circuit, encoder-supply short circuit, supply-voltage monitoring, configurable diagnostic alarms, and LED indications.
5. What connection and protection details should be verified before inquiry?
Verify the 2 4-pin D-coded M12 ports, the 8 encoder-supply outputs, the 24 V DC load-voltage range of 20.4 V to 28.8 V, and IP65/67/69K protection.