Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | F-DQ 8x24VDC/2A PPM |
| Digital outputs | 8 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Output current per channel | 2 A |
| Switching frequency with resistive load, max. | 30 Hz |
| Isolation | Between channels and backplane bus |
| Firmware update possible | Yes |
| Product lifecycle | Active Product |
Applications
- Digital input control: The digital output can control a digital input according to IEC 61131-2, type 2.
Key Features
- F-DQ digital outputs: The module has 8 digital outputs with current-sinking and current-sourcing capability.
- Output capacity: Output current is 2 A per channel; maximum switching capacity is 2 A with a resistive load and 10 W on a lamp load.
- 24 V supply: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC and reverse polarity protection.
- Diagnostics: Diagnostics include supply-voltage monitoring, wire-break detection, short-circuit detection, overload protection, diagnostic alarms, and Group error.
- Installation and cabling: The module has a 35 mm overall width. Maximum cable length is 1 000 m shielded or 500 m unshielded.
- Electrical isolation: Channels are isolated from the backplane bus; isolation is tested with 750 V DC (type test) and according to EN 50155 (routine test).
Frequently Asked Questions
1. What type of outputs does the 6AG2526-2BF00-1AB0 have?
It has 8 F-DQ digital outputs with current-sinking and current-sourcing capability.
2. What supply voltage does this module require?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC.
3. What is the maximum output current per channel?
The maximum output current per channel is 2 A.
4. What diagnostics are available?
The module provides supply-voltage monitoring, wire-break and short-circuit diagnostics, overload protection, diagnostic alarms, and Group error.