Product Overview

Technical Summary

Parameter Value
Module type F-DQ 8x24VDC/2A PPM
Digital outputs 8
Rated supply voltage 24 V DC
Permissible supply voltage 19.2 V to 28.8 V DC
Output current per channel 2 A
Switching frequency with resistive load, max. 30 Hz
Isolation Between channels and backplane bus
Firmware update possible Yes
Product lifecycle Active Product

Applications

  1. Digital input control: The digital output can control a digital input according to IEC 61131-2, type 2.

Key Features

  1. F-DQ digital outputs: The module has 8 digital outputs with current-sinking and current-sourcing capability.
  2. Output capacity: Output current is 2 A per channel; maximum switching capacity is 2 A with a resistive load and 10 W on a lamp load.
  3. 24 V supply: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC and reverse polarity protection.
  4. Diagnostics: Diagnostics include supply-voltage monitoring, wire-break detection, short-circuit detection, overload protection, diagnostic alarms, and Group error.
  5. Installation and cabling: The module has a 35 mm overall width. Maximum cable length is 1 000 m shielded or 500 m unshielded.
  6. Electrical isolation: Channels are isolated from the backplane bus; isolation is tested with 750 V DC (type test) and according to EN 50155 (routine test).

Frequently Asked Questions

1. What type of outputs does the 6AG2526-2BF00-1AB0 have?

It has 8 F-DQ digital outputs with current-sinking and current-sourcing capability.

2. What supply voltage does this module require?

The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC.

3. What is the maximum output current per channel?

The maximum output current per channel is 2 A.

4. What diagnostics are available?

The module provides supply-voltage monitoring, wire-break and short-circuit diagnostics, overload protection, diagnostic alarms, and Group error.