Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DI 8×24 V DC HF |
| Digital inputs | 8 |
| Rated input voltage | 24 V DC |
| Input voltage for signal 0 | -30 to +5 V |
| Input voltage for signal 1 | +11 to +30V |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Diagnostics | Channel-by-channel diagnostic alarm, wire-break and short-circuit diagnostics |
| BaseUnit | BU type A0 |
| Firmware version | V2.0 |
Applications
- Digital signal acquisition: Acquires 24 V DC digital signals through 8 parameterizable inputs with selectable edge evaluation and pulse extension.
Key Features
- Digital inputs: 8 parameterizable digital inputs with a 24 V DC rated input voltage.
- Input signal ranges: Signal 0: -30 to +5 V; signal 1: +11 to +30V.
- Input diagnostics: Channel-by-channel diagnostic alarms, wire-break and short-circuit diagnostics, and monitoring of the encoder power supply.
- Supply and protection: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Reverse polarity protection is included.
- Connection variants: 1-wire and 2-wire connections use BU type A0; 3-wire connections use BU type A0 with AUX terminals or a potential distributor module; 4-wire connections use BU type A0 + potential distributor module.
- Module identification: Firmware version V2.0, color code CC01, and mechanical coding element Type A.
Frequently Asked Questions
1. How many digital inputs does the 6AG1131-6BF00-7CA0 have?
It has 8 parameterizable digital inputs.
2. What input signal ranges does this module support?
Signal 0 is -30 to +5 V, and signal 1 is +11 to +30V.
3. What diagnostics are available?
The module provides channel-by-channel diagnostic alarms, wire-break diagnostics, short-circuit diagnostics, and encoder power-supply monitoring.
4. Which BaseUnit is used for the connection variants?