Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | IM 155-5 PN HF |
| Interface | PROFINET IO device; 1 interface with 2-port switch |
| Ethernet connection | 2x RJ45; 100BASE-TX; 100 Mbit/s full duplex |
| Supply voltage | 24 V DC rated; 19.2 V to 28.8 V DC permissible |
| Module capacity | Up to 12 I/O modules without PS; up to 30 with additional PS |
| IRT timing | 250 μs to 4 ms in 125 μs frame |
| Shortest clock pulse | 250 μs |
| Jitter, max. | 1 μs |
| Power | 14 W infeed to backplane bus |
| Protection | Reverse polarity and short-circuit protection |
| Redundancy | MRP, MRPD, and PROFINET system redundancy S2 |
| Isolation | 1500 V AC between PROFINET and all other circuits; type test |
Applications
- PROFINET IO device communication: Provides PROFINET IO device communication for ET 200MP electronic modules through its PROFINET interface.
Key Features
- PROFINET IO interface module: IM 155-5 PN HF device interface module for ET 200MP electronic modules, with PROFINET IO device and Open IE communication.
- 2-port Ethernet connection: Integrated 2-port switch with RJ45 interfaces, 100BASE-TX, 100 Mbit/s full duplex, autonegotiation, and autocrossing.
- Module capacity: Supports up to 12 I/O modules without PS and up to 30 I/O modules with additional PS.
- Supply and protection: Rated supply: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Reverse polarity and short-circuit protection are included.
- Timing and redundancy: IRT: 250 μs to 4 ms in 125 μs frame; shortest clock pulse: 250 μs; jitter, max.: 1 μs. Supports MRP, MRPD, and PROFINET system redundancy S2.
- Diagnostics and installation: RUN, ERROR, and MAINT LEDs, 2x green-yellow LINK TX/RX LEDs, hot swapping with active backplane bus, and a 0.356 kg net weight.
Frequently Asked Questions
1. What is the function of Siemens 6AG2155-5AA00-1AC0?
It is an IM 155-5 PN HF PROFINET IO device interface module for ET 200MP electronic modules.
2. How many ET 200MP I/O modules does it support?
It supports up to 12 I/O modules without PS and up to 30 I/O modules with additional PS.
3. What Ethernet connection does this module have?
It has 2x RJ45 ports through an integrated switch, with 100BASE-TX, 100 Mbit/s full duplex, autonegotiation, and autocrossing.