Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | F-RQ 1×24 V DC/24 … 230 V AC/5 A |
| Relay outputs | 1; 2 NO contacts |
| Rated coil voltage | 24 V DC |
| Resistive-load switching capacity, max. | 5 A |
| Lamp-load switching capacity, max. | 25 W |
| Output switching frequency with resistive load, max. | 2 Hz |
| Supply voltage permissible range | 20.4 V to 28.8 V DC |
| Relay coil current, max. | 70 mA |
| Horizontal installation total output current, max. | 5 A up to 40 °C |
| Potential difference, max. | 250 V AC (reinforced insulation) |
| Diagnostics | Green/red DIAG LED and green channel-status LED |
Applications
- Digital output control: Controls a digital input through its relay output.
Key Features
- Relay output and contacts: 1 relay output with 2 NO contacts; the output can control a digital input.
- Switching capacity: Maximum 5 A with resistive load and maximum 25 W with lamp load.
- Supply and coil: Rated supply voltage is 24 V DC; relay coil consumption is maximum 70 mA.
- Temperature and coating: Conformal coating; -30…+60 °C, OT1 with ST1/2 (+70 °C for 10 minutes).
- Diagnostics and isolation: Diagnostics function, green/red DIAG LED, green channel-status LED, and potential separation from the backplane bus.
- Installation and width: Rail-based module with 20 mm overall width; horizontal installation permits up to 5 A at up to 40 °C.
Frequently Asked Questions
1. What output does the Siemens 6AG2136-6RA00-1BF0 provide?
It provides 1 relay output with 2 NO contacts and can control a digital input.
2. What load can the relay output switch?
The maximum switching capacity is 5 A with resistive load and 25 W with lamp load.
3. What supply voltage does the relay coil use?
The relay coil has a rated supply voltage of 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.
4. What diagnostics does the module provide?
It provides a diagnostics function, a green/red DIAG LED, and a green channel-status LED.