Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | AQ 4xU/I ST |
| Analog outputs | 4; > +60 °C max. 2x ±10 V permissible |
| Output ranges | 0 to 10 V; 1 V to 5 V; -5 V to +5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution, max. | 16 bit including sign |
| Cycle time, all channels, min. | 5 ms |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V |
| Short-circuit current, max. | 45 mA |
| Load impedance | Voltage outputs, min. 2 kΩ; capacitive load, max. 1 μF; current outputs, max. 500 Ω |
| Diagnostics | Supply-voltage monitoring, diagnostic alarm, group error, overflow/underflow, wire break, and short circuit |
| Isolation | No isolation between channels; isolation from backplane bus and electronics power supply |
Applications
- Analog voltage output: Provides analog voltage outputs for connected actuators using two-wire or four-wire connections.
- Analog current output: Provides analog current outputs for connected actuators using two-wire connections.
Key Features
- Analog output channels: 4 analog voltage/current outputs; above +60 °C, a maximum of 2x ±10 V is permissible.
- Supported output ranges: Voltage: 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V. Current: 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- Resolution and cycle time: Maximum resolution is 16 bit including sign; minimum cycle time for all channels is 5 ms.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics and isolation: The module has supply-voltage monitoring, diagnostic alarm, group error, overflow/underflow, wire-break diagnostics for current outputs, and short-circuit diagnostics for voltage outputs. Channels are isolated from the backplane bus and electronics power supply.
- Connection and dimensions: Supports two-wire and four-wire voltage-output connections and two-wire current-output connections. Dimensions are 15 mm wide, 73 mm high, and 58 mm deep; weight is approximately 31 g.
Frequently Asked Questions
1. What output ranges does Siemens 6AG1135-6HD00-7BA1 support?
It supports 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V voltage outputs, plus 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA current outputs.
2. How many analog outputs does the module have?
It has 4 analog outputs. Above +60 °C, a maximum of 2x ±10 V is permissible.
3. What diagnostics are available?
It provides supply-voltage monitoring, diagnostic alarm, group error, overflow/underflow, wire-break diagnostics for current outputs, and short-circuit diagnostics for voltage outputs.
4. What supply voltage and connections are required?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. The module supports two-wire and four-wire voltage-output connections and two-wire current-output connections.