6AG1135-6HD00-7BA1

Siemens 6AG1135-6HD00-7BA1 SIPLUS ET 200SP analog output module with 4 voltage/current outputs, 16-bit resolution, 24 V supply, and diagnostics. Request a model-specific quote.

Product Code
6AG1135-6HD00-7BA1
Dimensions
7.7 × 6.5 × 2.3 cm
Weight
0.039 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type AQ 4xU/I ST
Analog outputs 4; > +60 °C max. 2x ±10 V permissible
Output ranges 0 to 10 V; 1 V to 5 V; -5 V to +5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Resolution, max. 16 bit including sign
Cycle time, all channels, min. 5 ms
Supply voltage 24 V DC; permissible range 19.2 V to 28.8 V
Short-circuit current, max. 45 mA
Load impedance Voltage outputs, min. 2 kΩ; capacitive load, max. 1 μF; current outputs, max. 500 Ω
Diagnostics Supply-voltage monitoring, diagnostic alarm, group error, overflow/underflow, wire break, and short circuit
Isolation No isolation between channels; isolation from backplane bus and electronics power supply

Applications

  1. Analog voltage output: Provides analog voltage outputs for connected actuators using two-wire or four-wire connections.
  2. Analog current output: Provides analog current outputs for connected actuators using two-wire connections.

Key Features

  1. Analog output channels: 4 analog voltage/current outputs; above +60 °C, a maximum of 2x ±10 V is permissible.
  2. Supported output ranges: Voltage: 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V. Current: 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
  3. Resolution and cycle time: Maximum resolution is 16 bit including sign; minimum cycle time for all channels is 5 ms.
  4. Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
  5. Diagnostics and isolation: The module has supply-voltage monitoring, diagnostic alarm, group error, overflow/underflow, wire-break diagnostics for current outputs, and short-circuit diagnostics for voltage outputs. Channels are isolated from the backplane bus and electronics power supply.
  6. Connection and dimensions: Supports two-wire and four-wire voltage-output connections and two-wire current-output connections. Dimensions are 15 mm wide, 73 mm high, and 58 mm deep; weight is approximately 31 g.

Frequently Asked Questions

1. What output ranges does Siemens 6AG1135-6HD00-7BA1 support?

It supports 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V voltage outputs, plus 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA current outputs.

2. How many analog outputs does the module have?

It has 4 analog outputs. Above +60 °C, a maximum of 2x ±10 V is permissible.

3. What diagnostics are available?

It provides supply-voltage monitoring, diagnostic alarm, group error, overflow/underflow, wire-break diagnostics for current outputs, and short-circuit diagnostics for voltage outputs.

4. What supply voltage and connections are required?

The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. The module supports two-wire and four-wire voltage-output connections and two-wire current-output connections.

Send Inquiry