Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | AQ 2xU/I HF |
| Analog outputs | 2 |
| Output signal ranges | 0 to 10 V; 1 V to 5 V; -5 V to +5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution | Up to 16 bit including sign |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Cycle time, all channels | 750 μs minimum |
| Diagnostics | Channel diagnostics, diagnostic alarm, supply-voltage monitoring, wire break, short-circuit, Group error, Overflow/Underflow |
| BaseUnits | BU type A0, A1 |
| Conformal coating | Yes; Class 2 for high reliability |
Applications
- Analog actuator signal output: Provides voltage or current output signals for connected actuators through two-wire voltage, four-wire voltage, or two-wire current connections.
Key Features
- Analog output channels: 2 analog outputs support voltage and current signals.
- Output ranges: Voltage ranges include 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V. Current ranges include 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- Resolution and cycle time: Resolution is up to 16 bit including sign; cycle time for all channels is 750 μs minimum.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics: The module has channel diagnostics, diagnostic alarms, supply-voltage monitoring, wire-break detection for current outputs, and short-circuit detection for voltage outputs.
- Installation and dimensions: The module supports BU type A0, A1 and has dimensions of 15 mm width, 73 mm height, and 58 mm depth.
Frequently Asked Questions
1. How many analog outputs does Siemens 6AG1135-6HB00-7CA1 have?
It has 2 analog outputs.
2. Which signal ranges does the module support?
It supports 0 to 10 V, 1 V to 5 V, -5 V to +5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
3. What supply voltage does the module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
4. What diagnostics are available?
It provides channel diagnostics, diagnostic alarms, supply-voltage monitoring, wire-break detection for current outputs, and short-circuit detection for voltage outputs.
5. Which BaseUnits can be used?
The module can be used with BU type A0 and A1.