6AG1134-6JD00-2CA1

Siemens 6AG1134-6JD00-2CA1 SIPLUS ET 200SP analog input module with 4 RTD/TC channels, 16-bit resolution, diagnostics, and 24 V supply. Request a model-specific quote.

Product Code
6AG1134-6JD00-2CA1
Dimensions
7.5 × 7 × 2.5 cm
Weight
0.041 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type AI 4xRTD/TC 2-/3-/4-wire HF
Analog input channels 4
Supported connections 2-wire, 3-wire, and 4-wire
Resolution 16 bit including sign
Rated supply 24 V DC
Permissible supply range 19.2 V to 28.8 V DC
Supported BaseUnits BU type A0, A1

Key Features

  1. Analog input channels: 4 analog inputs support RTD, thermocouple, resistance, and voltage measurement with 2-wire, 3-wire, or 4-wire connections.
  2. Signal ranges and resolution: Voltage input ranges include -1 V to +1 V, -250 mV to +250 mV, -50 mV to +50 mV, and -80 mV to +80 mV. Resolution is up to 16 bit including sign.
  3. Supply and electrical data: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Rated current consumption is 30 mA; typical power loss is 0.75 W.
  4. Diagnostics and isolation: The module has channel diagnostics, wire-break and overflow/underflow detection channel by channel, group error indication, and electrical isolation from the backplane bus and electronics supply.
  5. Installation and environmental data: It is suitable for BU type A0 and A1, has a 15 mm × 73 mm × 58 mm form factor, and supports horizontal operation from -40 °C to 60 °C or vertical operation from -40 °C to 50 °C.

Frequently Asked Questions

1. What input signals does Siemens 6AG1134-6JD00-2CA1 support?

It supports RTD, thermocouple, resistance, and voltage measurement. Voltage ranges include -1 V to +1 V, -250 mV to +250 mV, -50 mV to +50 mV, and -80 mV to +80 mV.

2. How many analog channels does this module have?

It has 4 analog inputs. Signal encoders can be connected using 2-wire, 3-wire, or 4-wire connections.

3. What diagnostics are available?

It has channel diagnostics, diagnostic and limit value alarms, supply-voltage monitoring, channel-by-channel wire-break and overflow/underflow detection, group error indication, and module and channel status LEDs.

4. What supply voltage does the module require?

The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Rated current consumption is 30 mA.

5. Which BaseUnits and installation conditions are supported?

It is suitable for BU type A0 and A1. Horizontal operation is supported from -40 °C to 60 °C, while vertical operation is supported from -40 °C to 50 °C.

Send Inquiry