Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | DQ 4×24 … 230 V AC/2 A HF |
| Digital outputs | 4 Triac outputs |
| Output current, signal "1", rated | 2 A |
| Output voltage, signal "1", min. | 20.4 V |
| Supply voltage, rated | 230 V AC; 47 … 63 Hz |
| Operating modes | DQ; DQ with energy-saving function; phase control; half-wave; full-wave |
| Diagnostics | Channel-by-channel open-circuit detection and wire-break diagnostics; group error; diagnostic alarms |
| BaseUnit | BU type U0 |
| Isolation | 2 545 V DC/2 s (routine test) |
| Product lifecycle | Active Product |
Applications
- Digital input control: The outputs can control a digital input.
Key Features
- Digital outputs: 4 parameterizable Triac outputs; current-sourcing is supported and current-sinking is not.
- Output voltage and current: Output voltage for signal "1": 20.4 V minimum; rated output current: 2 A, with a permissible range of 10 mA to 4 A.
- Operating modes: Supports DQ, DQ with energy-saving function, phase control from 8.5 … 100% of the phase angle, half-wave, and full-wave operation.
- Supply voltage: Rated supply voltage: 230 V AC at 47 … 63 Hz; permissible range: 20.4 V to 264 V.
- Diagnostics: Provides channel-by-channel open-circuit detection and wire-break diagnostics, diagnostic alarms, readable diagnostic information, group error, and LED indications.
- Installation and connection: Suitable for BU type U0; supports 1-wire and 2-wire connections with BU type U0, and 3-wire connection with BU type U0 plus Potential distributor module.
Frequently Asked Questions
1. How many digital outputs does Siemens 6AG1132-6FD00-7CU0 have?
It has 4 parameterizable Triac digital outputs.
2. What output voltage and current does this module support?
For signal "1", the minimum output voltage is 20.4 V. The rated output current is 2 A, with a permissible range of 10 mA to 4 A; derating data applies in the manual.
3. Which BaseUnit is required for this module?
It is suitable for BU type U0. 1-wire and 2-wire connections use BU type U0; 3-wire connection uses BU type U0 plus Potential distributor module.
4. What diagnostics are available?
It has channel-by-channel open-circuit detection and wire-break diagnostics, diagnostic alarms, readable diagnostic information, group error, supply-voltage monitoring, and LED indications.