Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | Digital output module, DQ 16x24VDC/0.5A ST |
| Digital outputs | 16 source outputs (PNP, current-sourcing) |
| Output current per channel | 0.5 A rated value; 0.5 A permissible maximum |
| Supply voltage | 24 V DC rated; 19.2 V to 28.8 V DC permissible range |
| Short-circuit protection | Electronic |
| Load resistance range | 48 Ω to 12 kΩ |
| Switching frequency, resistive load | 100 Hz maximum |
| Current consumption | 30 mA maximum; without load |
| Connection | BU type A0; AUX terminals or potential distributor module for 2-wire and 3-wire connections |
| Diagnostics | Supply voltage, wire break, short-circuit to ground, short-circuit to L+, and group error |
| Operating temperature | -40…+70 °C |
Applications
- Digital output control: Controls digital inputs through the module's source outputs.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
Key Features
- Digital output channels: 16 parameterizable source outputs (PNP, current-sourcing) with 0.5 A rated output current per channel.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. Reverse polarity protection is available.
- Output protection and diagnostics: Electronic short-circuit protection, open-circuit detection, diagnostic alarms, supply-voltage monitoring, wire-break and short-circuit diagnostics.
- Connection and coding: BU type A0 is used for 1-wire connections; BU type A0 with AUX terminals or a potential distributor module is used for 2-wire and 3-wire connections. Mechanical coding element: Type A.
- Switching and load data: Maximum switching capacity is 0.5 A with resistive or inductive load and 5 W with lamp load. Maximum switching frequency is 100 Hz with resistive load.
- Installation and protection details: Conformal coating, color code CC00, automatic encoding, I&M0 to I&M3 data, and isolation tested with 707 V DC (type test).
Frequently Asked Questions
1. How many digital outputs does Siemens 6AG1132-6BH01-7BA0 have?
It has 16 parameterizable source outputs (PNP, current-sourcing).
2. What supply voltage does this digital output module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. Which BaseUnit connections are supported?
BU type A0 is used for 1-wire connections. BU type A0 with AUX terminals or a potential distributor module is used for 2-wire and 3-wire connections.
4. What diagnostics are available?
The module supports supply-voltage monitoring, wire-break and short-circuit diagnostics, diagnostic alarms, and group error indication.