Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | DI 8xNAMUR HF |
| Digital inputs | 8; NAMUR |
| Supply voltage, rated | 24 V DC |
| NAMUR encoder supply | 8.2 V |
| Counting frequency, max. | 5 kHz |
| Channel diagnostics | Wire break and short circuit; channel by channel |
| BaseUnit | BU type A0 |
Applications
- Counter operation: The source supports counter operation with up to 4 counters, 5 kHz maximum counting frequency, 32-bit counting width, and selectable up/down counting direction.
- Gate start/stop input control: The parameterizable digital input functions include gate start/stop.
Key Features
- 8 NAMUR digital inputs: The module has 8 parameterizable digital inputs for NAMUR encoders and changeover contacts.
- Configurable input functions: Digital input functions include gate start/stop, freely usable digital input, and counter. Up to 4 counters are supported with a maximum counting frequency of 5 kHz and 32-bit counting width.
- Channel diagnostics: Diagnostics include channel-by-channel wire-break and short-circuit detection, diagnostic alarms, hardware interrupts on channels 0 to 7, and green/red DIAG indication.
- 24 V supply: The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC and reverse polarity protection. Maximum current consumption is 70 mA.
- NAMUR encoder supply: The module provides 8.2 V NAMUR encoder supply with short-circuit protection, up to 8 mA output current per channel and 64 mA per module.
Frequently Asked Questions
1. How many NAMUR inputs does the 6AG1131-6TF00-7CA0 have?
It has 8 parameterizable NAMUR digital inputs.
2. What supply voltage does this module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. Does the module support counter operation?
Yes. It supports up to 4 counters, a maximum counting frequency of 5 kHz, 32-bit counting width, and up/down counting.
4. What diagnostics are available?
It provides channel-by-channel wire-break and short-circuit detection, diagnostic alarms, hardware interrupts on channels 0 to 7, and supply-voltage monitoring.
5. Which BaseUnit and cable length are supported?
BU type A0 is supported for 2-wire and 3-wire connections. Shielded cable length is up to 200 m, or 50 m in Counter mode.