6ES7193-6BP20-0BB1

Siemens 6ES7193-6BP20-0BB1 SIMATIC ET 200SP BaseUnit with BU type B1, push-in terminals, 12 process terminals, and 24 V or 230 V supply options. Request a model-specific quote.

Product Code
6ES7193-6BP20-0BB1
Dimensions
12.1 × 4.3 × 3.4 cm
Weight
0.057 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type BU type B1
Process terminals 12; Pro slot
Supply voltage for P1 and P2 bus 24 V or 230 V
Supply voltage for AUX bus 24 V or 230 V
Supply voltage for process terminals 24 V or 230 V
Terminal type Push-in terminal
Current carrying capacity for process terminals, max. 5 A
Potential separation between backplane bus and supply voltage Yes
Automatic encoding Yes

Key Features

  1. BaseUnit type: BU20-P12+A0+4B with BU type B1; bridged to the left and without auxiliary terminals.
  2. Process terminals: 12 process terminals to the I/O module; 0 terminals to the AUX bus and 0 add-on terminals.
  3. Supply voltage: For P1 and P2 bus, AUX bus, and process terminals: 24 V or 230 V options. External protection for power supply lines: Yes.
  4. Push-in terminals: Push-in terminal type supports conductor cross-sections from 0.14 mm2 (AWG 26) to 2.5 mm2 (AWG 14).
  5. Current carrying capacity: Up to 60 °C, max.: 10 A. Process terminals, max.: 5 A; P1 and P2 bus and AUX bus, max.: 10 A.
  6. Dimensions and weight: Width: 20 mm; height: 117 mm; depth: 35 mm; weight, approx.: 48 g.

Frequently Asked Questions

1. What type of BaseUnit is Siemens 6ES7193-6BP20-0BB1?

It is a SIMATIC ET 200SP BaseUnit BU20-P12+A0+4B with BU type B1, bridged to the left and without auxiliary terminals.

2. How many process terminals does the BaseUnit have?

It has 12 process terminals to the I/O module; the source specifies Pro slot.

3. Which supply voltage options are listed?

For the P1 and P2 bus, AUX bus, and process terminals, the listed options are 24 V and 230 V.

4. What terminals and conductor sizes are supported?

It has push-in terminals for conductors from 0.14 mm2 (AWG 26) to 2.5 mm2 (AWG 14).

5. What should be verified before requesting a quote?

Verify the required supply voltage, process-terminal configuration, left-side bridging, and the exclusion of auxiliary terminals.

Send Inquiry