6ES7134-6JD00-0DA1

Siemens 6ES7134-6JD00-0DA1 SIMATIC ET 200SP analog input module with 4 thermocouple channels, 16-bit resolution, 24 V supply, and channel diagnostics. Request a model-specific quote.

Product Code
6ES7134-6JD00-0DA1
Dimensions
7.8 × 6.8 × 2.4 cm
Weight
0.04 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type AI 4xTC HS
Analog inputs 4
Input signal ranges -50 mV to +50 mV; -80 mV to +80 mV; -250 mV to +250 mV; -1 V to +1 V
Thermocouple types B, C, E, J, K, L, N, R, S, T, U, TXK/TXK(L) to GOST
Resolution 16 bit including sign
Supply voltage 24 V DC; 19.2 V to 28.8 V permissible range
Cycle time 5 ms minimum for all channels
BaseUnit connection BU type A0, A1; 2-wire connection
Diagnostics Wire break, overflow/underflow, limit value, supply voltage, and group error
Isolation Channels isolated from backplane bus and electronics power supply

Applications

  1. Temperature and voltage measurement: Acquires thermocouple temperature signals and voltage signals through 4 analog input channels, with adjustable temperature measurement units of °C, °F, or K.

Key Features

  1. Analog input channels: 4 analog inputs support thermocouple types B, C, E, J, K, L, N, R, S, T, U, and TXK/TXK(L) to GOST, plus voltage ranges from -50 mV to +50 mV, -80 mV to +80 mV, -250 mV to +250 mV, and -1 V to +1 V.
  2. Resolution and conversion: Resolution is up to 16 bit including sign. Conversion time per channel is 180/60/50/1.25 ms, with a minimum cycle time of 5 ms for all channels.
  3. Supply and connection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection. The module uses BU type A0 or A1 for 2-wire connection.
  4. Diagnostics: Channel diagnostics include wire-break detection and overflow/underflow monitoring channel by channel. The module also provides diagnostic, limit-value, supply-voltage, and group-error functions.
  5. Temperature compensation: Temperature compensation is parameterizable, with an internal comparison point available with BaseUnit type A1 and 4 reference channel groups.
  6. Isolation and accuracy: Channels are isolated from the backplane bus and the electronics power supply. Linearity error is +/-0.01% relative to the input range, and temperature error is +/-0.005%/K.

Frequently Asked Questions

1. How many analog input channels does the Siemens 6ES7134-6JD00-0DA1 have?

It has 4 analog input channels.

2. Which thermocouple types does the 6ES7134-6JD00-0DA1 support?

It supports types B, C, E, J, K, L, N, R, S, T, U, and TXK/TXK(L) to GOST.

3. What voltage input ranges are supported?

The supported ranges are -50 mV to +50 mV, -80 mV to +80 mV, -250 mV to +250 mV, and -1 V to +1 V.

4. What should be verified before requesting a quote for this module?

Verify the required signal range, thermocouple type, BU type A0 or A1 connection, 24 V DC supply, and cable length limits of 200 m for shielded cables or 100 m for thermocouples.

Send Inquiry