Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output type | Triac |
| Number of digital outputs | 4 |
| Output voltage for signal "1", min. | 20.4 V |
| Rated output current for signal "1" | 2 A |
| Output current for signal "1", permissible range | 10 mA to 4 A; note derating data in the manual |
| Rated supply voltage | 230 V AC; 47 … 63 Hz, max. rate of change of frequency 1 mHz/s |
| Switching capacity with resistive load, max. | 2 A; Max. 4 A, see additional description in manual |
| Current per module, max. | 8 A |
| Output delay with resistive load, max. | "0" to "1": 40 ms; "1" to "0": 20 ms |
| Channel diagnostics | Open-circuit detection and wire-break diagnosis, channel by channel |
| BaseUnit | BU type U0 |
Applications
- Digital output control: Controls a digital input and provides redundant control of a load through parallel switching of two outputs.
- Phase control: Provides phase control across 8.5 … 100% of the phase angle, with half-wave and full-wave operation.
Key Features
- Digital outputs: 4 parameterizable, current-sourcing Triac outputs; current-sinking is not supported.
- Output voltage and current: Output voltage for signal "1": 20.4 V minimum; rated output current: 2 A per channel, with a permissible range of 10 mA to 4 A and derating data in the manual.
- Operating modes: Supports DQ, DQ with energy-saving function, phase control, half-wave, and full-wave modes. Phase control covers 8.5 … 100% of the phase angle.
- Supply and power loss: Rated supply voltage: 230 V AC at 47 … 63 Hz; permissible supply range: 20.4 V to 264 V. Typical power loss is 9 W with a 230 V load voltage and all outputs loaded with 2 A at 50 Hz.
- Diagnostics: Provides channel-by-channel open-circuit detection and wire-break diagnosis, group error, diagnostic alarms, supply-voltage monitoring, and green/red diagnostic LEDs. Short-circuit protection and short-circuit diagnosis are not provided; external fusing is necessary.
- Connection and mounting context: Uses BU type U0 for 1-wire and 2-wire connections; a BU type U0 plus Potential distributor module is required for 3-wire connection. Horizontal installation supports 8 A up to 40 °C, while vertical installation supports 8 A up to 30 °C.
Frequently Asked Questions
1. What output type and channel count does Siemens 6ES7132-6FD00-0CU0 provide?
It has 4 parameterizable Triac digital outputs and supports current-sourcing, but not current-sinking.
2. What output voltage and current are supported?
The output voltage for signal "1" is 20.4 V minimum. Rated output current is 2 A per channel, with a permissible range of 10 mA to 4 A; note derating data in the manual.
3. Which BaseUnit is used for connection?
BU type U0 is used for 1-wire and 2-wire connections. A BU type U0 plus Potential distributor module is required for 3-wire connection.
4. Does the module provide channel diagnostics?
Yes. It provides channel-by-channel open-circuit detection and wire-break diagnosis, plus group error and diagnostic alarms. Short-circuit protection and short-circuit diagnosis are not provided.