Product Overview

Technical Summary

Parameter Value
Module type AQ 4xU/I ST
Number of analog outputs 4
Voltage output ranges 0 to 10 V; 1 V to 5 V; -5 V to +5 V; -10 V to +10 V
Current output ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Maximum resolution 16 bit including sign
Cycle time, all channels, min. 5 ms
Rated supply voltage 24 V DC
Permissible supply voltage 19.2 V to 28.8 V DC
Firmware version V1.1.3
Usable BaseUnits BU type A0, A1

Applications

  1. Analog output control: The module provides voltage and current output signals for connected actuators.

Key Features

  1. Analog outputs: 4 analog outputs support voltage ranges from -10 V to +10 V and current ranges from -20 mA to +20 mA.
  2. Resolution: Output resolution is up to 16 bit including sign.
  3. Supply voltage: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
  4. Diagnostics: The module has diagnostics, diagnostic alarms, group error indication, supply-voltage monitoring, and module diagnostics.
  5. Connections and loads: Voltage outputs support two-wire and four-wire connections; current outputs support two-wire connections. Voltage output load impedance is min. 2 kΩ, and current output load is max. 500 Ω.
  6. Installation and dimensions: The module is suitable for BU type A0 and A1, with automatic and Type A mechanical coding. Dimensions are 15 mm × 73 mm × 58 mm.

Frequently Asked Questions

1. How many analog outputs does 6ES7135-6HD00-0BA1 have?

It has 4 analog outputs.

2. Which voltage and current ranges are supported?

Voltage ranges are 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.

3. What is the maximum output resolution?

The maximum resolution is 16 bit including sign.

4. What diagnostics are available?

The module has module diagnostics, diagnostic alarms, group error indication, supply-voltage monitoring, wire-break diagnosis for current outputs, and short-circuit diagnosis for voltage outputs.

5. Which BaseUnits can be used?

The module is suitable for BU type A0 and A1.