Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DQ 16x110VDC ST |
| Digital outputs | 16 transistor outputs |
| Rated output current | 0.5 A per channel; 0.5 A per group |
| Maximum module current | 8 A |
| Rated DC output voltage | 24 V; 48 V; 72 V; 96 V; 110 V; 125 V |
| Rated AC output voltage | 24 V; 48 V (50 – 60 Hz) |
| Maximum resistive-load switching frequency | 25 Hz |
| Backplane bus power consumption | 2 W |
| Power loss, typ. | 3.8 W |
| Isolation test | 2 000 V DC (type test) and according to EN 50155 (routine test) |
Applications
- Digital output control: The module provides parameterizable transistor outputs for controlling digital loads.
- Digital input control: The module can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Key Features
- 16 transistor outputs: The module has 16 parameterizable digital transistor outputs with both current-sinking and current-sourcing operation.
- Output current: Rated output current is 0.5 A per channel and 0.5 A per group; maximum current per module is 8 A.
- Rated output voltage: Rated DC output values are 24 V, 48 V, 72 V, 96 V, 110 V, and 125 V. Rated AC output values are 24 V and 48 V at 50 – 60 Hz.
- Output switching: Maximum switching frequency is 25 Hz with resistive load, 0.5 Hz with inductive load, and 10 Hz on lamp load.
- Status and isolation: RUN, ERROR, channel status, and module diagnostics LEDs are provided. Channels are electrically separated in groups of 1 and separated from the backplane bus.
- SIPLUS protection: The module has conformal coating and a -40…+70 °C specification, with OT4 and ST1/2 at +85 °C for 10 minutes.
Frequently Asked Questions
1. How many digital outputs does the Siemens 6AG2522-5EH00-4AB0 have?
It has 16 parameterizable transistor outputs.
2. What output current does the module support?
The rated output current is 0.5 A per channel and 0.5 A per group. Maximum current per module is 8 A.
3. Which output voltage values are supported?
Rated DC output values are 24 V, 48 V, 72 V, 96 V, 110 V, and 125 V. Rated AC output values are 24 V and 48 V (50 – 60 Hz).
4. What diagnostics are available?
RUN, ERROR, channel status, and module diagnostics LEDs are available. The diagnostics function and diagnostic alarm are not available.
5. What should be verified before requesting a quote?
Verify the required load type, output voltage, current per channel and group, cable length, and mounting or installation requirements.