Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | DQ 16x24VDC/0.5A HF |
| Digital output channels | 16 transistor outputs in groups of 8 |
| Rated supply voltage | 24 VDC |
| Permissible supply voltage | 19.2 V to 28.8 VDC |
| Rated output voltage | 24 VDC |
| Current per channel, max. | 0.5 A |
| Current per group, max. | 4 A |
| Current per module, max. | 8 A |
| Output delay, max. | 100 μs for "0" to "1"; 500 μs for "1" to "0" with resistive load |
| Diagnostics | Supply voltage, wire break, short-circuit, and group error monitoring |
| Conformal coating | Yes; -40…+70 °C, OT4 with ST1/2 (+85 °C for 10 minutes) |
Applications
- Digital output control: The module provides current-sourcing transistor outputs for controlling digital outputs and can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Key Features
- Digital output channels: 16 current-sourcing transistor outputs, parameterizable, arranged in groups of 8.
- Output ratings: 0.5 A per channel, 4 A per group, and 8 A per module maximum; resistive load switching is 0.5 A maximum.
- Supply and output voltage: Rated supply voltage is 24 VDC with a permissible range of 19.2 V to 28.8 V. Rated output voltage is 24 VDC.
- Diagnostics and status: Single-channel diagnostics include supply-voltage monitoring, wire-break, short-circuit, and group error detection. Diagnostic, maintenance, RUN, ERROR, MAINT, PWR, and channel-status indications are provided.
- Installation and protection: Conformal coating; short-circuit protection is electronically clocked. Shielded cable length is up to 1 000 m and unshielded cable length is up to 600 m.
Frequently Asked Questions
1. What output type and channel count does 6AG2522-1BH01-4AB0 have?
It has 16 current-sourcing transistor outputs in groups of 8.
2. What supply voltage does the module require?
The rated supply voltage is 24 VDC, with a permissible range of 19.2 V to 28.8 VDC.
3. What output current limits should be checked?
The maximum current is 0.5 A per channel, 4 A per group, and 8 A per module. The manual provides additional description.
4. Which diagnostics are available?
Diagnostics cover supply-voltage monitoring, wire break, short-circuit, and group error. Substitute values, diagnostic alarms, and maintenance interrupts are supported.