Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | TM Count 2x24V |
| Channels | 2 |
| Encoder and pulse-generator signal | 24 V |
| Digital inputs | 6; 3 per channel |
| Digital outputs | 4 transistor outputs; 2 per channel |
| Counting frequency, max. | 800 kHz; with quadruple evaluation |
| Frequency measurement range | 0.04 Hz to 800 kHz |
| Mounting | S7-1500 mounting rail |
Applications
- Incremental encoder counting: Counts signals from 24 V incremental encoders, including A/B tracks with 90° phase offset and zero track.
- Pulse measurement: Measures frequency and cycle duration from pulse generators and incremental encoder signals.
- Counter control: Supports hardware and software gates, event-controlled stop, synchronization via digital input, and comparison-value switching.
Key Features
- 2-channel counter module: 2 channels support 24 V incremental encoders or pulse generators, with 2 counters and a maximum counting frequency of 800 kHz with quadruple evaluation.
- Digital I/O per channel: Each channel has 3 parameterizable digital inputs and 2 parameterizable transistor outputs.
- 24 V supply and encoder supply: Rated load voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V. One common 24 V encoder supply serves both channels, with a maximum total encoder current of 1 A.
- Encoder and measurement functions: Supports A/B-track incremental encoders, pulse encoders, frequency measurement from 0.04 Hz to 800 kHz, and cycle duration measurement from 1.25 μs to 25 s.
- Diagnostics and mounting: Provides diagnostic alarms, hardware interrupts, supply-voltage monitoring, wire-break and short-circuit diagnostics, and mounting on an S7-1500 mounting rail.
- SIPLUS conformal coating: Has conformal coating for high reliability, with operation from -40 °C to 70 °C for horizontal installation and -40 °C to 40 °C for vertical installation.
Frequently Asked Questions
1. What signals does Siemens 6AG1550-1AA01-7AB0 support?
It supports 24 V incremental encoders and pulse generators, including A/B-track incremental encoders and pulse encoders with direction.
2. How many channels and counters does the module have?
It has 2 channels and 2 counters. Each channel provides 3 digital inputs and 2 transistor outputs.
3. What is the maximum counting frequency?
The maximum counting frequency is 800 kHz with quadruple evaluation.
4. How is the module mounted?
It is mounted on an S7-1500 mounting rail.