Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | AI 8xU/R/RTD/TC HF |
| Analog inputs | 8; plus one additional RTD (reference) channel |
| Resolution | 16 bit; up to 21 bit with overrange for RTC and TC in scalable temperature measuring range |
| Accuracy | 0.1% |
| Rated supply | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Voltage input ranges | -1 V to +1 V; -25 mV to +25 mV; -250 mV to +250 mV; -50 mV to +50 mV; -500 mV to +500 mV; -80 mV to +80 mV |
| Maximum current consumption | 55 mA; with 24 V DC supply |
Applications
- Analog signal measurement: Measures voltage, resistance, resistance thermometer, and thermocouple signals through its analog input channels.
- Signal diagnostics: Monitors supply voltage, wire breaks for TC, R, and RTD, limit values, overflow/underflow, and channel or module diagnostics.
Key Features
- Analog input channels: 8 analog inputs support voltage, resistance, resistance thermometer, and thermocouple measurement, plus one additional RTD reference channel.
- Signal ranges: Supported ranges include -1 V to +1 V, -25 mV to +25 mV, -250 mV to +250 mV, -50 mV to +50 mV, -500 mV to +500 mV, and -80 mV to +80 mV; 4 mA to 20 mA is not supported.
- Resolution and accuracy: Analog input resolution is 16-bit, with 0.1% accuracy and 21 bit resolution with overrange for RTC and TC measuring modes when using the scalable temperature measuring range.
- Supply and consumption: Rated supply is 24 V DC with a permissible range of 19.2 V to 28.8 V DC. Maximum current consumption is 55 mA with 24 V DC supply, and power consumption from the backplane bus is 0.85 W.
- Diagnostics and isolation: The module has diagnostic alarms, limit value alarms, supply-voltage monitoring, wire-break detection for TC, R, and RTD, overflow/underflow detection, and potential separation between channels in groups of 1.
- Connection and installation: The supplied hardware includes an infeed element, shielding bracket, and shield terminal. Shielded cable length is up to 800 m at U and 200 m at R/RTD/TC.
Frequently Asked Questions
1. How many analog inputs does the 6AG1531-7PF00-4AB0 have?
It has 8 analog inputs plus one additional RTD reference channel.
2. Which signal types does this module measure?
It measures voltage, resistance, resistance thermometer, and thermocouple signals.
3. What supply voltage does the module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
4. What diagnostics are available?
Diagnostics include diagnostic and limit value alarms, supply-voltage monitoring, wire-break detection for TC, R, and RTD, overflow/underflow detection, and channel or module diagnostic LEDs.