6AG1531-7KF00-7AB0

Siemens 6AG1531-7KF00-7AB0 SIPLUS analog input module has 8 channels, 16-bit resolution, U/I/RTD/TC inputs and 24 V supply. Request a model-specific quote.

Product Code
6AG1531-7KF00-7AB0
Dimensions
16 × 19 × 4.3 cm
Weight
0.418 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type AI 8xU/I/RTD/TC ST
Analog input channels 8; > +60 °C max. 2x ±20 mA or 4x ±10 V or 4x RTD permissible
Resolution with overrange 16 bit
Rated supply 24 V DC
Permissible supply range 19.2 V to 28.8 V DC
Supported voltage ranges 1 V to 5 V; -1 V to +1 V; -10 V to +10 V; -2.5 V to +2.5 V; -250 mV to +250 mV; -5 V to +5 V; -50 mV to +50 mV; -500 mV to +500 mV; -80 mV to +80 mV
Supported current ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Basic error limit at 25 °C 0.1% for voltage, current and resistance relative to input range
Common mode voltage, max. 10 V

Applications

  1. Analog signal acquisition: Measures voltage, current, resistance, RTD and thermocouple signals through its analog input channels.
  2. Signal diagnostics: Performs supply-voltage monitoring, wire-break detection, limit value alarms and overflow/underflow detection for supported input types.

Key Features

  1. Analog input channels: 8 analog input channels; voltage and current measurement use 8 channels, while resistance and resistance thermometer measurement use 4 channels.
  2. Supported signals: Supports 1 V to 5 V, -1 V to +1 V, -10 V to +10 V, -2.5 V to +2.5 V, -250 mV to +250 mV, -5 V to +5 V, -50 mV to +50 V, -500 mV to +500 mV, -80 mV to +80 mV, 0 to 20 mA, -20 mA to +20 mA, 4 mA to 20 mA, resistance ranges, RTD types and thermocouple types B, E, J, K, N, R, S and T.
  3. Resolution and accuracy: Resolution with overrange is 16 bit. Collected product accuracy is 0.3%; the basic error limit at 25 °C is 0.1% for voltage, current and resistance relative to the input range.
  4. Diagnostics and alarms: Has diagnostics, diagnostic and limit value alarms, supply-voltage monitoring, wire-break detection for 1 V to 5 V, 4 mA to 20 mA, TC, R and RTD, overflow/underflow detection, and RUN, ERROR, PWR and channel-status LEDs.
  5. Supply and protection: Rated supply is 24 V DC with a permissible range of 19.2 V to 28.8 V and reverse polarity protection. Common mode voltage is limited to 10 V.
  6. Connection and installation items: Includes an infeed element, shielding bracket and shield terminal. Shielded cable length is max. 800 m for U/I, 200 m for R/RTD, and 50 m for TC.

Frequently Asked Questions

1. What input signals does Siemens 6AG1531-7KF00-7AB0 support?

It supports voltage, current, resistance, RTD and thermocouple measurement, including 1 V to 5 V, 4 mA to 20 mA, resistance ranges, RTD types and thermocouple types B, E, J, K, N, R, S and T.

2. How many analog channels does this module have?

It has 8 analog input channels. At > +60 °C, max. 2x ±20 mA or 4x ±10 V or 4x RTD is permissible.

3. What supply does the module require?

The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC and reverse polarity protection.

4. What diagnostics are available?

It has diagnostics, diagnostic and limit value alarms, supply-voltage monitoring, supported wire-break detection, overflow/underflow detection, and RUN, ERROR, PWR and channel-status LEDs.

5. What is included for shielded installation?

The configuration includes an infeed element, shielding bracket and shield terminal. Shielded cable length is max. 800 m for U/I, 200 m for R/RTD, and 50 m for TC.

Send Inquiry