| Parameter | Value |
|---|---|
| Product type | F-DI 16x24VDC |
| Digital input channels | 16 |
| Input voltage, signal 0 | -30 to +5 V |
| Input voltage, signal 1 | +15 to +30 V |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 to 28.8 V DC |
| Standard input transition time | 0.4 ms to 20 ms |
| Isolation test voltage | 707 V DC |
| Product lifecycle | Active Product |
Key Features
- Digital input channels: 16 digital inputs with sourcing/sinking input and P-reading.
- Input signal ranges: Signal 0: -30 to +5 V; signal 1: +15 to +30 V.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 to 28.8 V DC. Reverse polarity protection is included.
- Diagnostics: Diagnostics, diagnostic alarm, supply-voltage monitoring, short-circuit detection, and group error indication are supported. Wire-break detection and hardware interrupt are not supported.
- Timing and cable length: Standard inputs have parameterizable 0 to 1 and 1 to 0 times from 0.4 ms to 20 ms. Maximum cable length is 1 000 m shielded or 500 m unshielded.
- Isolation and installation: Channels are isolated from the backplane bus; isolation is tested with 707 V DC. Overall width is 35 mm.
Frequently Asked Questions
1. How many digital inputs does the 6AG1526-1BH00-2AB0 have?
It has 16 digital inputs.
2. What input signal ranges does this F-DI module support?
Signal 0 is -30 to +5 V, and signal 1 is +15 to +30 V.
3. What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 to 28.8 V DC.
4. Which diagnostics are available?
It supports diagnostics, diagnostic alarms, supply-voltage monitoring, short-circuit detection, and group error indication. Wire-break detection and hardware interrupts are not supported.
5. What should be verified before requesting a quote?