Product Overview

Technical Summary

Parameter Value
Product type F-DI 16x24VDC
Digital input channels 16
Input voltage, signal 0 -30 to +5 V
Input voltage, signal 1 +15 to +30 V
Rated supply voltage 24 V DC
Permissible supply voltage 19.2 to 28.8 V DC
Standard input transition time 0.4 ms to 20 ms
Isolation test voltage 707 V DC
Product lifecycle Active Product

Key Features

  1. Digital input channels: 16 digital inputs with sourcing/sinking input and P-reading.
  2. Input signal ranges: Signal 0: -30 to +5 V; signal 1: +15 to +30 V.
  3. Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 to 28.8 V DC. Reverse polarity protection is included.
  4. Diagnostics: Diagnostics, diagnostic alarm, supply-voltage monitoring, short-circuit detection, and group error indication are supported. Wire-break detection and hardware interrupt are not supported.
  5. Timing and cable length: Standard inputs have parameterizable 0 to 1 and 1 to 0 times from 0.4 ms to 20 ms. Maximum cable length is 1 000 m shielded or 500 m unshielded.
  6. Isolation and installation: Channels are isolated from the backplane bus; isolation is tested with 707 V DC. Overall width is 35 mm.

Frequently Asked Questions

1. How many digital inputs does the 6AG1526-1BH00-2AB0 have?

It has 16 digital inputs.

2. What input signal ranges does this F-DI module support?

Signal 0 is -30 to +5 V, and signal 1 is +15 to +30 V.

3. What supply voltage does the module require?

The rated supply voltage is 24 V DC, with a permissible range of 19.2 to 28.8 V DC.

4. Which diagnostics are available?

It supports diagnostics, diagnostic alarms, supply-voltage monitoring, short-circuit detection, and group error indication. Wire-break detection and hardware interrupts are not supported.

5. What should be verified before requesting a quote?

Verify the required cable type and length, mounting arrangement, terminal details, and the required diagnostics functions for the exact configuration.