Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output type | Relays |
| Number of digital outputs | 16 |
| Channel grouping | In groups of 2 |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Rated output voltage | 230 V AC |
| Rated output current for signal "1" | 2 A |
| Power loss, typ. | 5 W |
| Conformal coating | -40…+70 °C; start up -25 °C |
Applications
- Digital output control: The relay outputs support controlling digital inputs and logic links.
- Redundant load control: The module supports redundant control of a load.
Key Features
- Relay digital outputs: 16 parameterizable relay outputs, arranged in groups of 2; current-sinking and current-sourcing are supported.
- Output voltage and current: Rated output voltage: 230 V AC; supported output voltage: 24 V DC to 120 V DC / 24 V AC to 230 V AC. Rated output current for signal "1": 2 A.
- 24 V DC supply: Rated supply voltage: 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics and status: Diagnostic alarms, maintenance interrupts, supply-voltage monitoring, substitute values, and RUN, ERROR, MAINT, PWR, and channel status LEDs are available.
- Isolation and grouping: Channels are not isolated from each other and are isolated in groups of 2; channels are isolated from the backplane bus and load voltage L+.
Frequently Asked Questions
1. What output type and channel count does the 6AG1522-5HH00-7AB0 have?
It has 16 parameterizable relay digital outputs in groups of 2.
2. What supply voltage does this module require?
Its rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. What output voltage and current are supported?
The rated output voltage is 230 V AC. The rated output current for signal "1" is 2 A.
4. What diagnostics are available?
It has diagnostic alarms, maintenance interrupts, supply-voltage monitoring, substitute values, and RUN, ERROR, MAINT, PWR, and channel status LEDs.