Technical Summary
| Parameter | Value |
|---|---|
| Module type | DQ 16x230VAC/1A ST (Triac) |
| Digital outputs | 16 |
| Output arrangement | 16 channels in groups of 2 |
| Rated output voltage | 230 V; 120/230 V AC, 50/60 Hz |
| Rated current per channel | 1 A |
| Maximum current per group | 2 A |
| Maximum current per module | 10 A; see additional description in the manual |
| Backplane bus power consumption | 1.2 W |
| Power loss, typical | 11.1 W |
| Output protection | 6.3 A melting fuse, slow-blow |
Applications
- AC load switching: Switch AC loads through the 16 Triac digital outputs, with a maximum switching frequency of 10 Hz for resistive load, 0.5 Hz for inductive load, and 1 Hz for lamp load.
- Redundant load control: Use parallel switching of two outputs for redundant control of a load.
Key Features
- Digital output channels: 16 Triac digital outputs, arranged in groups of 2; outputs are parameterizable.
- AC output rating: Rated output voltage: 230 V; 120/230 V AC, 50/60 Hz. Rated current per channel: 1 A.
- Output load capacity: Maximum switching capacity is 1 A with resistive load and 50 W on lamp load. Maximum current per group is 2 A.
- Output status and module LEDs: RUN LED: green; ERROR LED: red; channel status display: green LED; module diagnostics: red LED.
- Substitute values and maintenance: Substitute values are connectable. Maintenance interrupt is available for the switching cycle counter.
- Electrical separation: The channels are not separated from each other, but are separated from the backplane bus. Permissible potential difference is 250 V AC between channels and the backplane bus, and 500 V AC between channels.
Frequently Asked Questions
1. How many outputs does the Siemens 6AG1522-5FH00-7AB0 have?
It has 16 Triac digital outputs arranged in groups of 2.
2. What output voltage and current does this module support?
The rated output voltage is 230 V; 120/230 V AC, 50/60 Hz. Rated current is 1 A per channel, with a maximum of 2 A per group.
3. Does the module provide substitute values and diagnostics?
Substitute values are connectable. It has green RUN and channel-status LEDs, a red ERROR LED, and a red module-diagnostics LED.