Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | DQ 16x24VDC/0.5A HF |
| Digital output channels | 16 |
| Output type | Current-sourcing transistor |
| Output rated voltage | 24 VDC |
| Output current per channel | 0.5 A rated value; 0.5 A maximum |
| Maximum current per group | 4 A |
| Maximum current per module | 8 A |
| Output delay with resistive load | 100 μs from "0" to "1"; 500 μs from "1" to "0" |
| Diagnostics | Supply voltage, wire break, short circuit, and group error |
| Channel and bus isolation | Channels not separated from each other; channels separated from backplane bus |
Applications
- Digital output control: Controls digital loads through 16 transistor outputs and supports parallel switching for logic links and redundant control of a load.
Key Features
- Digital output channels: 16 current-sourcing transistor outputs; the outputs are parameterizable and conform to IEC 61131, type 0.5.
- Output supply and current: Output rated value: 24 VDC. Signal "1" output current: 0.5 A rated value and 0.5 A permissible maximum.
- Group current capacity: Maximum current: 4 A per group and 8 A per module; the source notes additional details in the manual.
- Diagnostics: Diagnostics include supply-voltage monitoring, wire-break, short-circuit, and group error detection, with diagnostic and maintenance alarms.
- Isolation and channel grouping: The channels are not electrically separated from each other; separation between the channels and backplane bus is provided. Channels are arranged in groups of 8.
- Timing and protection: Output delay with resistive load is up to 100 μs from "0" to "1" and up to 500 μs from "1" to "0". Short-circuit protection is electronically clocked.
Frequently Asked Questions
1. How many digital outputs does the 6AG1522-1BH01-7AB0 have?
It has 16 current-sourcing transistor outputs.
2. What output voltage and current does this module provide?
The output rated voltage is 24 VDC. Signal "1" output current is 0.5 A rated value and 0.5 A maximum.
3. What diagnostics are available?
It provides supply-voltage monitoring, wire-break, short-circuit, and group error diagnostics, plus diagnostic and maintenance alarms.
4. What is the maximum current per output group?
The maximum current is 4 A per group; the source notes additional details in the manual.