Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DQ 8x24VDC/2A HF |
| Digital outputs | 8 transistor outputs, current-sourcing |
| Rated supply voltage | 24 V DC |
| Permissible supply-voltage range | 19.2 V to 28.8 V DC |
| Rated output current for signal "1" | 2 A per channel |
| Maximum total current | 8 A per group; 16 A per module |
| PWM outputs | Up to 2 |
| PWM duty-cycle resolution | 0.1 % |
| Minimum PWM pulse duration | 300 μs |
| Isolation tested with | 707 V DC (type test) |
Applications
- Digital output control: The module controls digital outputs and can control a digital input.
- PWM output control: The module provides parameterizable PWM output, including logic links and redundant control of a load.
Key Features
- Digital outputs: 8 current-sourcing transistor outputs; outputs are parameterizable and arranged in groups of 8.
- Output current: Signal "1" rated output current: 2 A per channel; maximum total current is 8 A per group and 16 A per module.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC.
- PWM operation: PWM output is supported with up to 2 outputs, 2 … 100 ms parameterizable cycle duration, 0.1 % duty-cycle resolution and 300 μs minimum pulse duration; FS02 and FW V2.1.0 or higher.
- Diagnostics: Diagnostics, diagnostic and maintenance alarms, supply-voltage monitoring, short-circuit and group-error diagnostics, and connectable substitute values are supported.
- Isolation and protection: The channels are not electrically isolated from each other, but are isolated from the backplane bus; short-circuit and reverse-polarity protection are provided.
Frequently Asked Questions
1. How many digital outputs does 6AG1522-1BF00-7AB0 have?
It has 8 current-sourcing transistor outputs arranged in groups of 8.
2. What supply voltage does this module require?
Its rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. Does the module support PWM output?
Yes. Up to 2 PWM outputs are supported with FS02 and FW V2.1.0 or higher; the cycle duration is parameterizable from 2 … 100 ms.
4. What diagnostics are available?
It supports diagnostics, diagnostic and maintenance alarms, supply-voltage monitoring, short-circuit and group-error diagnostics, and connectable substitute values.