6AG2232-4HD32-1XB0

Siemens 6AG2232-4HD32-1XB0 SIPLUS S7-1200 analog output module with 4 AQ, +/-10 V or 0 to 20 mA, diagnostics and 24 V supply. Request a model-specific quote.

Product Code
6AG2232-4HD32-1XB0
Dimensions
10.6 × 9 × 5.6 cm
Weight
0.19 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1232 AQ 4x 14 bit
Analog outputs 4; Current or voltage
Voltage output range -10 V to +10 V
Current output range 0 to 20 mA
Voltage resolution 14 bit
Current resolution 13 bit
Rated supply voltage 24 V DC
Typical power loss 1.5 W
Protection rating IP20

Applications

  1. Analog signal output: Provides 4 analog voltage or current output signals.

Key Features

  1. Analog output channels: 4 analog outputs for current or voltage signals.
  2. Supported output ranges: Voltage: -10 V to +10 V; current: 0 to 20 mA.
  3. Resolution: Voltage resolution: 14 bit; current resolution: 13 bit.
  4. Diagnostics: Alarms, diagnostic alarms, supply-voltage monitoring, wire-break and short-circuit monitoring are supported.
  5. Supply and consumption: Rated supply voltage: 24 V DC. Typical current consumption: 45 mA; backplane bus consumption: 80 mA from 5 V DC.
  6. Protection and isolation: IP20 protection. Isolation is tested with 750 V DC type test and according to EN 50155 routine test.

Frequently Asked Questions

1. How many analog outputs does the 6AG2232-4HD32-1XB0 have?

It has 4 analog outputs for current or voltage signals.

2. Which output ranges are supported?

Voltage outputs support -10 V to +10 V, and current outputs support 0 to 20 mA.

3. What resolution does the module provide?

The resolution is 14 bit for voltage and 13 bit for current.

4. What diagnostics are available?

The module supports alarms, diagnostic alarms, supply-voltage monitoring, wire-break monitoring, short-circuit monitoring, and output-status LEDs.

5. What supply voltage does it require?

The rated supply voltage is 24 V DC.