Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Integrated digital inputs | 8; 24 V DC |
| Integrated digital outputs | 6; 24 V DC |
| Analog inputs | 2; 0 to +10 V |
| PROFINET interfaces | 1; RJ 45 Ethernet |
| PROFINET transmission rate, max. | 100 Mbit/s |
| Supply voltage | 24 V DC; 20.4 V to 28.8 V DC |
| Typical current consumption | 400 mA |
| High-speed outputs | 4; 100 kHz Pulse Train Output |
| Position-controlled positioning axes, max. | 8 |
| Degree of protection | IP20 |
Applications
- Digital signal acquisition: Acquires digital signals through 8 integrated 24 V DC inputs.
- Digital output control: Controls digital loads through 6 integrated 24 V DC outputs.
- PROFINET communication: Performs PROFINET IO Controller and IO device communication through the integrated PROFINET interface.
- Position-controlled positioning: Supports controlled positioning for up to 8 positioning axes and provides 4 positioning axes through a pulse-direction interface.
Key Features
- Integrated I/O: Has 8 digital inputs, 6 digital outputs and 2 analog inputs with a 0 to +10 V voltage range; analog outputs: 0.
- PROFINET communication: Has 1 isolated PROFINET interface with an RJ 45 Ethernet port, up to 100 Mbit/s, and PROFINET IO Controller and IO device functions.
- CPU supply: Rated supply is 24 V DC with a permissible range of 20.4 V to 28.8 V DC; typical current consumption is 400 mA.
- High-speed functions: Has 4 high-speed outputs at 100 kHz, 6 counters with a maximum counting frequency of 100 kHz, and controlled positioning for up to 8 axes.
- Installation and protection: Dimensions are 90 mm × 100 mm × 75 mm, approximate weight is 370 g, and the degree of protection is IP20.
- SIPLUS environmental design: Operating temperature is -25 °C to 60 °C for horizontal installation and -25 °C to 50 °C for vertical installation; +70 °C is available for 10 minutes under OT1, ST1/ST2 conditions.
Frequently Asked Questions
1. How many integrated I/O channels does the Siemens 6AG2212-1AE40-1XB0 have?
It has 8 digital inputs, 6 digital outputs and 2 analog inputs. It has 0 analog outputs.
2. What PROFINET interface does this CPU have?
It has 1 isolated PROFINET interface with 1 RJ 45 Ethernet port and a maximum transmission rate of 100 Mbit/s.
3. What supply voltage does the CPU require?
The rated supply is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.