Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS S7-1200 SM 1223, DI 16×24 V DC, DQ 16x relay |
| Digital inputs | 16 |
| Digital outputs | 16 relay outputs |
| Input voltage | 24 V DC; signal "0": 5 V DC at 1 mA; signal "1": 15 V DC at 2.5 mA |
| Output voltage | 5 V DC to 30 V DC; 5 V AC to 250 V AC |
| Output switching capacity | 2 A with resistive load |
| Input delay | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
| Supply voltage | 24 V DC; permissible range 20.4 V to 28.8 V |
| Protection | IP20 |
Applications
- Digital signal acquisition: The 16 digital inputs acquire 24 V DC signals with sink/source capability.
- Relay output control: The 16 relay outputs switch connected loads with a resistive-load switching capacity of 2 A.
Key Features
- Digital I/O: 16 digital inputs and 16 relay outputs; inputs are 24 V DC, sink/source, and outputs have 2 A switching capacity with resistive load.
- Input signal levels: Input voltage is 5 V DC at 1 mA for signal "0" and 15 V DC at 2.5 mA for signal "1".
- Output voltage ranges: Relay output voltage is 5 V DC to 30 V DC or 5 V AC to 250 V AC.
- Diagnostics and isolation: Diagnostic alarm and input/output status LEDs are provided. Digital outputs are isolated from the backplane bus at 1 500 V AC for 1 minute.
- Timing and connection: Input delays are parameterizable from 0.2 ms to 12.8 ms in the listed selectable values, and a front connector is required.
- Rail and environmental protection: The module has conformal coating, IP20 protection, and an ambient operating range of -25 °C to 60 °C, with +70 °C for 10 min under the stated OT1, ST1/ST2 conditions.
Frequently Asked Questions
1. How many digital inputs and relay outputs does the 6AG2223-1PL32-1XB0 have?
It has 16 digital inputs and 16 relay outputs.
2. What input signals does this module support?
The inputs are 24 V DC, sink/source. Signal "0" is 5 V DC at 1 mA, and signal "1" is 15 V DC at 2.5 mA.
3. What output voltage and switching capacity are provided?
The relay outputs support 5 V DC to 30 V DC and 5 V AC to 250 V AC. Switching capacity is 2 A with a resistive load.
4. Does the module provide diagnostics and isolation?
Yes. It has a diagnostic alarm, input and output status LEDs, and 1 500 V AC isolation from the backplane bus for 1 minute.
5. What should be verified before requesting a quote?
Verify the 24 V DC supply, required front connector, mounting conditions, ambient temperature limits, and the stated output load restrictions.