6AG2222-1HF32-1XB0

Siemens 6AG2222-1HF32-1XB0 SIPLUS SM 1222 module with 8 relay outputs, 24 V relay coils, and 2 A rated output current. Request a model-specific quote.

Product Code
6AG2222-1HF32-1XB0
Dimensions
11.2 × 8.8 × 5.6 cm
Weight
0.186 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SM 1222, DQ 8x relay/2 A
Digital outputs 8 relay outputs, in groups of 2
Rated relay-coil supply 24 V DC
Rated output voltage 5 V DC to 30 V DC; 5 V AC to 250 V AC
Rated output current 2 A for signal "1"
Protection IP20
Operating ambient temperature -25 °C to 60 °C; +70 °C for 10 minutes under OT1, ST1/ST2 according to EN 50155

Applications

  1. Relay output control: The 8 relay outputs provide digital switching for connected loads within the stated output voltage and switching-capacity limits.
  2. Output status diagnostics: The module provides a diagnostic alarm and LED indication for output status.

Key Features

  1. 8 relay outputs: The SM 1222 provides 8 digital relay outputs in groups of 2.
  2. Output switching capacity: Switching capacity is up to 2 A with resistive load and up to 30 W with DC or 200 W with AC lamp load.
  3. Output voltage ranges: Rated output voltage is 5 V DC to 30 V DC or 5 V AC to 250 V AC.
  4. Supply and power loss: The relay coils have a rated supply voltage of 24 V DC. Typical power loss is 4.5 W.
  5. Diagnostics and isolation: The module has a diagnostic alarm, output-status LED indication, relay potential separation between channels in groups of 2, and 1 500 V AC isolation from the backplane bus for 1 minute.
  6. SIPLUS environmental protection: The module has conformal coating, IP20 protection, and an operating ambient temperature of -25 °C to 60 °C; +70 °C is permitted for 10 minutes under OT1, ST1/ST2 according to EN 50155.

Frequently Asked Questions

1. How many relay outputs does the Siemens 6AG2222-1HF32-1XB0 have?

It has 8 digital relay outputs in groups of 2.

2. What output voltage and current are supported?

The rated output voltage is 5 V DC to 30 V DC or 5 V AC to 250 V AC, with 2 A rated output current for signal "1".

3. What supply voltage do the relay coils require?

The relay coils have a rated supply voltage of 24 V DC.

4. What diagnostics are available?

The module has a diagnostic alarm and an LED for output status.

5. What should be verified before requesting a quote?

Verify the required output voltage, load type, switching capacity, cable length, and installation temperature conditions.