6AG1232-4HD32-2XB0

Siemens 6AG1232-4HD32-2XB0 SIPLUS SM 1232 analog output module with 4 AQ, ±10 V or 0 to 20 mA, and 24 V supply. Request a model-specific quote.

Product Code
6AG1232-4HD32-2XB0
Dimensions
10.5 × 8.8 × 6 cm
Weight
0.179 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1232, AQ 4×14 bit
Based on 6ES7232-4HD32-0XB0
Analog outputs 4; Current or voltage
Voltage output range -10 V to +10 V
Current output range 0 to 20 mA
Voltage resolution 14 bit
Current resolution 13 bit
Rated supply voltage 24 V DC
Front connector Required
Protection IP20

Applications

  1. Analog signal output: Provides analog voltage or current outputs through 4 channels.

Key Features

  1. Analog outputs: 4 analog outputs; current or voltage.
  2. Output ranges: Voltage: -10 V to +10 V; current: 0 to 20 mA.
  3. Resolution: Voltage: 14 bit; current: 13 bit.
  4. Supply and consumption: Rated supply voltage: 24 V DC; current consumption, typ.: 45 mA; backplane bus consumption at 5 V DC, typ.: 80 mA.
  5. Diagnostics: Alarms, diagnostic function, diagnostic alarm, supply-voltage monitoring, wire-break and short-circuit detection.
  6. Installation and protection: Required front connector, 45 mm x 100 mm x 75 mm, IP20 protection, and 180 g approximate weight.

Frequently Asked Questions

1. What output signals does 6AG1232-4HD32-2XB0 support?

It supports voltage outputs from -10 V to +10 V and current outputs from 0 to 20 mA.

2. How many analog output channels does the module have?

It has 4 analog outputs, configurable for current or voltage.

3. What resolution is available for the output signals?

Voltage outputs have 14 bit resolution; current outputs have 13 bit resolution.

4. What diagnostics are available?

It has alarms, a diagnostic function, diagnostic alarms, supply-voltage monitoring, wire-break detection, short-circuit detection, and output-status LEDs.