6AG1231-5PF32-4XB0

Siemens 6AG1231-5PF32-4XB0 SIPLUS SM 1231 RTD module with 8 resistance thermometer inputs, 24 V supply, diagnostics and IP20 protection. Request a model-specific quote.

Product Code
6AG1231-5PF32-4XB0
Dimensions
10.5 × 8.3 × 8.8 cm
Weight
0.286 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1231, AI 8×16 bit RTD
Analog inputs 8; Resistance thermometer
Rated supply voltage 24 V DC
Typical input current 40 mA
Typical backplane bus current 80 mA at 5 V DC
Resistance input ranges 0 to 150 ohms; 0 to 300 ohms; 0 to 600 ohms
Resolution with overrange 15 bit; + sign
Measurement principle integrating
Front connector Required
IP degree of protection IP20

Applications

  1. Resistance thermometer temperature measurement: Measures temperature using supported Pt, Ni and Cu resistance thermometers, with temperature units adjustable in degrees Celsius or degrees Fahrenheit.

Key Features

  1. RTD analog inputs: 8 analog inputs for resistance thermometers, including Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100 and LG-Ni1000.
  2. Resistance ranges: Supports resistance input ranges of 0 to 150 ohms, 0 to 300 ohms and 0 to 600 ohms.
  3. Resolution and measurement: Integrating measurement principle with 15 bit resolution including sign; temperature units are adjustable in degrees Celsius or degrees Fahrenheit.
  4. Diagnostics: Has alarms, readable diagnostics, supply-voltage monitoring, wire-break detection and input-status and maintenance LEDs.
  5. Supply and power: Rated supply voltage: 24 V DC. Typical input current is 40 mA, backplane bus current is 80 mA at 5 V DC, and typical power loss is 1.5 W.
  6. Conformal coating and protection: Has conformal coating for high reliability and IP20 protection.

Frequently Asked Questions

1. How many RTD inputs does the 6AG1231-5PF32-4XB0 have?

It has 8 analog inputs for resistance thermometers.

2. Which resistance thermometers are supported?

Supported types include Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100 and LG-Ni1000.

3. What supply voltage does the module require?

The rated supply voltage is 24 V DC.

4. What diagnostics are available?

It has alarms, readable diagnostics, supply-voltage monitoring, wire-break detection and LEDs for input status and maintenance.

5. What connector and protection details should be checked before inquiry?

A front connector is required, and the module has IP20 protection.

Send Inquiry