6AG1231-5PD32-4XB0

Siemens 6AG1231-5PD32-4XB0 SIPLUS S7-1200 SM 1231 RTD module has 4 resistance-thermometer inputs and 24 V supply. Request a model-specific quote.

Product Code
6AG1231-5PD32-4XB0
Dimensions
10.5 × 9 × 5.7 cm
Weight
0.197 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SM 1231, AI 4×16 bit RTD
Analog input channels 4; Resistance thermometer
Supported resistance thermometer types Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000
Rated supply voltage 24 V
Resolution with overrange 15 bit; + sign
Diagnostics Supply-voltage monitoring, wire-break detection, readable diagnostics, alarms
Required connection Front connector
Operating ambient temperature -20 °C to 60 °C

Key Features

  1. RTD analog inputs: 4 analog inputs for resistance thermometers, including Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, and LG-Ni1000.
  2. Resistance ranges: Supports 0 to 150 ohms, 0 to 300 ohms, and 0 to 600 ohms.
  3. Resolution and conversion: Resolution with overrange is 15 bit; + sign. The measurement principle is integrating, with 85 dB interference voltage suppression at 50 / 60 / 400 Hz.
  4. Diagnostics: Has alarms, readable diagnostics, supply-voltage monitoring, wire-break detection, and input-status and maintenance LEDs.
  5. Supply and connection: Rated supply voltage is 24 V. Current consumption is 40 mA typical, backplane bus consumption is 80 mA typical, and a front connector is required.
  6. Protection and dimensions: Has conformal coating, IP20 protection, and dimensions of 45 mm width, 100 mm height, and 75 mm depth.

Frequently Asked Questions

1. How many RTD inputs does the 6AG1231-5PD32-4XB0 have?

It has 4 analog inputs for resistance thermometers.

2. Which resistance thermometer types are supported?

It supports Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, and LG-Ni1000.

3. What connection does the module require?

It requires a front connector.

Send Inquiry