6AG1223-3BD30-5XB0

Siemens 6AG1223-3BD30-5XB0 SIPLUS SB 1223 I/O module with 2 DI/2 DQ, 24 V DC and 200 kHz digital channels. Request a model-specific quote.

Product Code
6AG1223-3BD30-5XB0
Dimensions
8 × 5 × 3 cm
Weight
0.031 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SB 1223, DI 2×24 V DC/DQ 2×24 V DC 200 kHz
Digital inputs 2; current-sourcing
Digital outputs 2; MOSFET, solid-state (current-sinking/current-sourcing)
Rated input voltage 24 V DC
Rated output voltage 24 V DC
Output current 0.1 A rated; 0.1 A maximum permissible
Input status diagnostics LED: Yes
Output status diagnostics LED: Yes

Key Features

  1. Digital I/O: 2 current-sourcing digital inputs and 2 MOSFET solid-state digital outputs with current-sinking/current-sourcing.
  2. Input voltage: Rated input voltage: 24 V DC; input signal 0: (L+ minus 5.0 V DC) … L+; input signal 1: 0 V … (L+ minus 10 V DC).
  3. Output rating: Rated output voltage: 24 V DC; output current for signal 1: 0.1 A rated and 0.1 A maximum permissible.
  4. Signal timing: Digital input standard delay is parameterizable from 0.1 μs to 20.0 μs or from 0.05 ms to 20.0 ms.
  5. Diagnostics and connection: LED diagnostics indicate input and output status. Shielded cable length is maximum 50 m; the cable is shielded, twisted pair for the stated input connection.
  6. SIPLUS construction: Conformal coating is provided, with operation from -40 °C to 60 °C and start-up at -25 °C.

Frequently Asked Questions

1. What I/O does Siemens 6AG1223-3BD30-5XB0 provide?

It provides 2 current-sourcing digital inputs and 2 MOSFET solid-state digital outputs with current-sinking/current-sourcing.

2. What are the rated signal voltages?

The rated input and output voltages are 24 V DC.

3. What output current is supported?

The output current for signal 1 is 0.1 A rated, with a 0.1 A maximum permissible range.

4. Does the module provide I/O diagnostics?

Yes. LED diagnostics indicate the status of the inputs and the outputs.

5. What should be verified before requesting a quote?

Verify the required I/O count, signal timing, cable connection, 50 m cable limit, dimensions, and the stated -40 °C to 60 °C operating range.