6AG1223-1PL32-2XB0

Siemens 6AG1223-1PL32-2XB0 SIPLUS SM 1223 module with 16 digital inputs, 16 relay outputs, 24 V signals, and IP20 protection. Request a model-specific quote.

Product Code
6AG1223-1PL32-2XB0
Dimensions
10.5 × 8.3 × 8.8 cm
Weight
0.325 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SM 1223, DI 16×24 V DC, DQ 16x relay
Digital inputs 16; 24 V DC; sink/source; groups of 2
Relay outputs 16; groups of 4
Input voltage for signal "0" 5 V DC at 1 mA
Input voltage for signal "1" 15 V DC at 2.5 mA
Output voltage 5 V DC to 30 V DC; 5 V AC to 250 V AC
Output current 2 A rated value for signal "1"
Supply voltage 24 V DC; 20.4 V to 28.8 V permissible range
Diagnostics Diagnostic alarm; LEDs for input and output status
Protection IP20
Operating temperature -40 °C to +70 °C; start-up at -25 °C

Applications

  1. Digital signal acquisition: Acquires digital signals through 16 digital inputs with 24 V DC input signals.
  2. Relay output switching: Switches loads through 16 relay outputs with resistive-load switching capacity up to 2 A.

Key Features

  1. Digital inputs: 16 digital inputs, 24 V DC, sink/source, arranged in groups of 2; input characteristic curve according to IEC 61131, type 1.
  2. Relay outputs: 16 relay outputs with 5 V DC to 30 V DC or 5 V AC to 250 V AC output voltage and 2 A rated output current.
  3. Supply: Rated supply voltage: 24 V DC; permissible range: 20.4 V to 28.8 V.
  4. Diagnostics: Diagnostic alarm and LED indications for input and output status.
  5. Protection and coating: IP20 protection; conformal coating according to EN 61086, Class 2 for high reliability.
  6. Installation and dimensions: Required front connector; 70 mm width, 100 mm height, and 75 mm depth.

Frequently Asked Questions

1. How many digital inputs and relay outputs does 6AG1223-1PL32-2XB0 have?

It has 16 digital inputs and 16 relay outputs.

2. What input signals does this module support?

The inputs are 24 V DC, sink/source, with 5 V DC at 1 mA for signal "0" and 15 V DC at 2.5 mA for signal "1".

3. What output voltage and current are supported?

The output voltage is 5 V DC to 30 V DC or 5 V AC to 250 V AC. The rated output current for signal "1" is 2 A.

4. Does the module provide diagnostics?

Yes. It has a diagnostic alarm and LEDs for input and output status.

5. What should be verified before requesting a quote?

Verify the required front connector, supply range of 20.4 V to 28.8 V, mounting dimensions of 70 mm x 100 mm x 75 mm, and the required load type.

Send Inquiry