Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SM 1223, DI 16×24 V DC, DQ 16x relay |
| Digital inputs | 16; 24 V DC; sink/source; groups of 2 |
| Relay outputs | 16; groups of 4 |
| Input voltage for signal "0" | 5 V DC at 1 mA |
| Input voltage for signal "1" | 15 V DC at 2.5 mA |
| Output voltage | 5 V DC to 30 V DC; 5 V AC to 250 V AC |
| Output current | 2 A rated value for signal "1" |
| Supply voltage | 24 V DC; 20.4 V to 28.8 V permissible range |
| Diagnostics | Diagnostic alarm; LEDs for input and output status |
| Protection | IP20 |
| Operating temperature | -40 °C to +70 °C; start-up at -25 °C |
Applications
- Digital signal acquisition: Acquires digital signals through 16 digital inputs with 24 V DC input signals.
- Relay output switching: Switches loads through 16 relay outputs with resistive-load switching capacity up to 2 A.
Key Features
- Digital inputs: 16 digital inputs, 24 V DC, sink/source, arranged in groups of 2; input characteristic curve according to IEC 61131, type 1.
- Relay outputs: 16 relay outputs with 5 V DC to 30 V DC or 5 V AC to 250 V AC output voltage and 2 A rated output current.
- Supply: Rated supply voltage: 24 V DC; permissible range: 20.4 V to 28.8 V.
- Diagnostics: Diagnostic alarm and LED indications for input and output status.
- Protection and coating: IP20 protection; conformal coating according to EN 61086, Class 2 for high reliability.
- Installation and dimensions: Required front connector; 70 mm width, 100 mm height, and 75 mm depth.
Frequently Asked Questions
1. How many digital inputs and relay outputs does 6AG1223-1PL32-2XB0 have?
It has 16 digital inputs and 16 relay outputs.
2. What input signals does this module support?
The inputs are 24 V DC, sink/source, with 5 V DC at 1 mA for signal "0" and 15 V DC at 2.5 mA for signal "1".
3. What output voltage and current are supported?
The output voltage is 5 V DC to 30 V DC or 5 V AC to 250 V AC. The rated output current for signal "1" is 2 A.
4. Does the module provide diagnostics?
Yes. It has a diagnostic alarm and LEDs for input and output status.
5. What should be verified before requesting a quote?
Verify the required front connector, supply range of 20.4 V to 28.8 V, mounting dimensions of 70 mm x 100 mm x 75 mm, and the required load type.