6AG1222-1HH32-2XB0

Siemens 6AG1222-1HH32-2XB0 SIPLUS SM 1222 module with 16 relay outputs, 2 A switching capacity, and 24 V relay coils. Request a model-specific quote.

Product Code
6AG1222-1HH32-2XB0
Dimensions
11.2 × 8.8 × 5.6 cm
Weight
0.26 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1222, DQ 16x relay/2 A
Digital outputs 16 relay outputs
Relay coil supply voltage 24 V DC
Supply voltage permissible range 20.4 V to 28.8 V DC
Output voltage, DC 5 V DC to 30 V DC
Output voltage, AC 5 V AC to 250 V AC
Output current for signal "1" 2 A
Output delay, "0" to "1" 10 ms maximum with resistive load
Output delay, "1" to "0" 10 ms maximum with resistive load
Protection IP20; short-circuit protection must be provided externally

Key Features

  1. Digital outputs: 16 relay outputs, arranged in groups of 1.
  2. Switching capacity: Maximum 2 A with resistive load and maximum 30 W with DC or 200 W with AC lamp load.
  3. Output voltage: Rated output voltage ranges from 5 V DC to 30 V DC or from 5 V AC to 250 V AC.
  4. Supply and power: Relay coil rated supply voltage is 24 V; typical power loss is 8.5 W.
  5. Diagnostics and protection: Diagnostic alarm and output-status LED indication are available. Short-circuit protection is not provided and must be provided externally.
  6. Installation and dimensions: The module requires a front connector, has IP20 protection, and measures 45 mm wide, 100 mm high, and 75 mm deep.

Frequently Asked Questions

1. How many relay outputs does the 6AG1222-1HH32-2XB0 have?

It has 16 relay outputs.

2. What output voltage ranges does this module support?

The rated output voltage is 5 V DC to 30 V DC or 5 V AC to 250 V AC.

3. What is the relay coil supply voltage?

The rated relay coil supply voltage is 24 V DC.

4. Does the module include short-circuit protection?

No. Short-circuit protection must be provided externally.

5. What connector and protection details should be verified before inquiry?

The module requires a front connector and has IP20 protection.

Send Inquiry