Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | CM 4 x IO-Link ST |
| IO-Link ports | 4; 4 simultaneously controllable |
| IO-Link protocols | IO-Link protocol 1.0 and 1.1 |
| Rated supply voltage | 24 V DC |
| Supply voltage range | 19.2 V to 28.8 V DC; 20.5 V minimum when IO-Link is used |
| Transmission rates | 4.8 kBaud (COM1); 38.4 kBaud (COM2); 230.4 kBaud (COM3) |
| Process data size | Input: 32 byte max. per port, 144 byte max. per module; output: 32 byte max. per port, 128 byte max. per module |
Applications
- IO-Link device communication: The module provides IO-Link master communication for connected IO-Link devices through its 4 ports.
- Digital signal operation: The module supports DI and DQ operating modes for digital input and output operation.
Key Features
- IO-Link master ports: 4 IO-Link ports are available, and all 4 ports can be controlled simultaneously. Port types A and B are supported; port type B provides 24 V DC via an external terminal.
- Operating modes: IO-Link, DI, and DQ operation are supported. DQ output current is limited to 100 mA per channel.
- Supply voltage: Rated supply: 24 V DC. The permissible range is 19.2 V to 28.8 V DC; 20.5 V is required when IO-Link is used.
- IO-Link communication: IO-Link protocol 1.0 and 1.1 are supported. Transmission rates are 4.8 kBaud (COM1), 38.4 kBaud (COM2), and 230.4 kBaud (COM3).
- Diagnostics and protection: The module has supply-voltage monitoring, wire-break, short-circuit, and group-error diagnostics, plus green PWR, channel-status, red Fn, and green/red DIAG LEDs. Reverse-polarity and short-circuit protection are provided.
- Rail installation and dimensions: The module is rail-based and measures 15 mm wide, 73 mm high, and 58 mm deep. Horizontal operation is supported from -40 °C to 60 °C; +70 °C is supported for 10 minutes under OT2, ST1/ST2 conditions.
Frequently Asked Questions
1. How many IO-Link ports does Siemens 6AG2137-6BD00-1BA0 have?
It has 4 IO-Link ports, of which 4 can be controlled simultaneously.
2. Which IO-Link protocols and transmission rates are supported?
IO-Link protocol 1.0 and 1.1 are supported, with 4.8 kBaud (COM1), 38.4 kBaud (COM2), and 230.4 kBaud (COM3).
3. What supply voltage does the module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. When IO-Link is used, the lower limit is 20.5 V.
4. What diagnostics are available?
Supply-voltage monitoring, wire-break, short-circuit, and group-error diagnostics are available, with PWR, channel-status, Fn, and DIAG LEDs.