6AG2137-6AA01-4BA0

SIPLUS ET 200SP CM PtP communications module for RS-422, RS-485 and RS-232 serial connections, with Freeport and Modbus RTU. Request a model-specific quote.

Product Code
6AG2137-6AA01-4BA0
Dimensions
7.8 × 6.4 × 2.3 cm
Weight
0.04 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type CM PtP
Serial interfaces RS-422, RS-485 and RS-232
Connection Push-in terminal
Supported communication Freeport, 3964 (R), USS and Modbus RTU master or slave
Maximum transmission rate 250 kbit/s
Rated supply voltage 24 V DC
Permissible supply voltage 19.2 V to 28.8 V DC
Current consumption 31 mA rated; 35 mA maximum

Applications

  1. Serial communication: Provides serial connection communication through RS-422, RS-485 and RS-232 interfaces.
  2. Modbus RTU communication: Supports Modbus RTU master and Modbus RTU device communication, with an address area of 1 to 247 and extended 1 to 65535.

Key Features

  1. Serial interfaces: Supports RS-422, RS-485 and RS-232 with a Push-in terminal connection.
  2. Communication protocols: Supports Freeport, 3964 (R), USS and Modbus RTU master or slave communication.
  3. Transmission rate: Maximum transmission rate is 250 kbit/s for RS-485 and 115.2 kbit/s for RS-232 and RS-422.
  4. Power supply: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
  5. Diagnostics and isolation: Provides diagnostics, diagnostic alarm, wire-break diagnosis, green PWR, green/red DIAG, green RxD and green TxD LEDs, plus potential separation between the backplane bus and interface.
  6. SIPLUS environmental design: Conformal coating is provided for high reliability, with horizontal operating temperatures from -40 °C to 70 °C and +85 °C for 10 minutes under OT4, ST1/ST2 conditions according to EN 50155.

Frequently Asked Questions

1. Which serial interfaces does the 6AG2137-6AA01-4BA0 support?

It supports RS-422, RS-485 and RS-232 serial interfaces.

2. Which communication protocols are supported?

It supports Freeport, 3964 (R), USS and Modbus RTU master or slave communication.

3. What supply voltage does the module require?

The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.

4. What connection does the module use?

The connection is a Push-in terminal.

Send Inquiry