Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | F-PM-E PPM 24VDC |
| Safe shutdown function | 24 V DC safe shutdown of DQ and F-DQ up to PL D/SIL2 or PL E/SIL3 |
| Safety protocol | PROFIsafe |
| Safe digital inputs | 2 |
| Safe digital outputs | 1 |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 20.4 V to 28.8 V DC |
| BaseUnits | BU type C0 |
| Input address space | 7 byte |
| Output address space | 5 byte |
| Product lifecycle | Active Product |
| Conformal coating | -30…+60 °C, OT1 with ST1/2 (+70 °C für 10 minutes) |
Applications
- Safe shutdown of outputs: Provides 24 V DC safe shutdown of DQ and F-DQ through PROFIsafe up to PL D/SIL2 or PL E/SIL3.
- Safe digital signal handling: Handles 2 safe digital inputs and 1 safe digital output.
Key Features
- Fail-safe power module: F-PM-E PPM 24VDC provides 24 V DC safe shutdown of DQ and F-DQ through PROFIsafe up to PL D/SIL2 or PL E/SIL3.
- Safe digital channels: The module has 2 safe digital inputs and 1 safe digital output.
- 24 V DC supply: Rated supply voltage is 24 V, with a permissible range of 20.4 V to 28.8 V and reverse polarity protection.
- Diagnostics and status LEDs: Diagnostics include diagnostic alarms, I&M0 to I&M3 data, RUN, ERROR, PWR, channel-status, channel-diagnostics, and DIAG LEDs.
- Installation and protection: The module is based on 6ES7136-6PA00-0BC0, uses BU type C0 BaseUnits, and has conformal coating for -30…+60 °C, OT1 with ST1/2 (+70 °C für 10 minutes).
Frequently Asked Questions
1. How many safe digital channels does 6AG2136-6PA00-1BC0 have?
It has 2 safe digital inputs and 1 safe digital output.
2. What supply voltage does the module use?
The rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.
3. What safety function is provided?
It provides 24 V DC safe shutdown of DQ and F-DQ through PROFIsafe up to PL D/SIL2 or PL E/SIL3.
4. Which BaseUnits are usable?
The usable BaseUnits are BU type C0.
5. What should be verified before ordering this configuration?
Verify the F-PM-E PPM 24VDC type, BU type C0 BaseUnits, safe channel count, supply range, and PROFIsafe function.