Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | AI 4x U/I 2-wire |
| Analog inputs | 4; > 60 °C max. 1x ±20 mA or 4x ±10 V permissible |
| Voltage input ranges | 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -5 V to +5 V |
| Current input ranges | 0 to 20 mA; 4 mA to 20 mA |
| Resolution | Up to 16 bit including sign |
| Rated supply | 24 V DC |
| Supply range | 19.2 V to 28.8 V DC |
| Encoder supply output | Max. 20 mA; max. 50 mA per channel for a duration < 10 s |
| Conversion time | 180 / 60 / 50 ms per channel |
| BaseUnit | BU type A0, A1 |
| Protection and diagnostics | Conformal coating; module diagnostics; reverse polarity and encoder-supply short-circuit protection |
Applications
- Voltage measurement: Measures voltage signals through the supported analog voltage input ranges.
- 2-wire current measurement: Measures current signals from 2-wire transducers through the supported current input ranges.
- Signal diagnostics: Monitors supply voltage and detects wire breaks, short circuits, group errors, and overflow/underflow.
Key Features
- Analog input channels: 4 analog inputs support voltage ranges from -10 V to +10 V and current ranges from 0 to 20 mA and 4 mA to 20 mA.
- Resolution and conversion: Resolution is up to 16 bit including sign; conversion time per channel is 180 / 60 / 50 ms.
- Supply and encoder output: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. The 24 V encoder supply has short-circuit protection and an output current of max. 20 mA.
- Signal connections: The module supports voltage measurement and 2-wire transducers for current measurement. 4-wire current measurement is not supported.
- Diagnostics and isolation: Diagnostics include supply-voltage monitoring, wire-break detection at 4 mA to 20 mA, short-circuit detection, group error, overflow/underflow, and diagnostic alarms. Isolation is tested with 750 V DC (type test).
- Mounting and configuration: The module is suitable for BU type A0 and A1, uses mechanical coding element Type A, and supports automatic encoding and reparameterization in RUN.
Frequently Asked Questions
1. How many analog inputs does the 6AG2134-6HD01-4BA1 have?
It has 4 analog inputs. Above 60 °C, max. 1x ±20 mA or 4x ±10 V is permissible.
2. Which signal ranges does this module support?
Voltage ranges are 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V. Current ranges are 0 to 20 mA and 4 mA to 20 mA.
3. What supply voltage does the module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
4. Which diagnostics are available?
The module provides supply-voltage monitoring, wire-break detection at 4 mA to 20 mA, short-circuit detection, group error, overflow/underflow, and diagnostic alarms.
5. Which BaseUnits can be used for connection?
The module is suitable for BU type A0 and A1.