Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | SIPLUS ET 200SP relay module |
| Digital output channels | 4 |
| Output type | Relays; normally open |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Maximum current per channel | 5 A |
| Maximum current per module | 20 A |
| Contact switching capacity | 5 A resistive load; 2 A inductive load |
| Relay rated switching voltage | 24 V DC to 120 V DC; 24V AC to 230V AC |
| BaseUnit connection | BU type B1 for 2-wire connection; BU type B0 for 3-wire connection |
| Diagnostics | Supply-voltage monitoring, group error, diagnostic alarm, and module diagnostics |
| Firmware update | Yes |
Applications
- Relay output switching: Switch loads through the 4 digital relay outputs, with separate limits for resistive and inductive loads.
- Output status and fault diagnostics: Monitor supply voltage, group errors, output status, and module diagnostics through the supported diagnostic functions and LEDs.
Key Features
- Relay outputs: 4 digital relay outputs support current-sinking, current-sourcing, and parameterizable operation.
- Output current: Maximum current is 5 A per channel and 20 A per module. For horizontal installation, the maximum module current is 20 A up to 50 °C, 16 A up to 60 °C, or 12 A up to 70 °C.
- Relay switching capacity: Contact switching capacity is maximum 5 A with resistive load and 2 A with inductive load. Rated switching voltage is 24 V DC to 120 V DC or 24V AC to 230V AC.
- Supply and protection: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC and reverse polarity protection.
- Diagnostics: The module has diagnostics, diagnostic alarms, supply-voltage monitoring, group error detection, substitute values, a green PWR LED, and a green/red DIAG LED.
- BaseUnit and connection: Use BU type B1 for 2-wire connection or BU type B0 for 3-wire connection. The module is suitable for BU type B0 or B1.
Frequently Asked Questions
1. How many digital outputs does the Siemens 6AG2132-6MD00-4BB1 have?
It has 4 digital relay outputs.
2. What supply voltage does this relay module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
3. What output current is supported?
The maximum current is 5 A per channel and 20 A per module. Installation and temperature restrictions apply to the maximum module current.
4. Which BaseUnit is used for connection?
Use BU type B1 for 2-wire connection or BU type B0 for 3-wire connection.