Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output type | Relays |
| Number of digital outputs | 4 |
| Supply voltage | 24 V DC rated; permissible range 19.2 V DC to 28.8 V DC |
| Rated switching voltage (DC) | 24 V DC to 120 V DC |
| Rated switching voltage (AC) | 24 V AC to 230 V AC |
| Maximum current per channel | 5 A; above +60 °C, maximum continuous current per relay 3 A |
| Maximum current per module | 20 A |
| Connection | 2-wire with BU type B1; 3-wire with BU type B0 |
| Diagnostics | Supply-voltage monitoring, diagnostic alarm, substitute values, and module diagnostics |
| Protection | Reverse polarity protection; no short-circuit protection |
| Isolation | 240 V AC permissible potential difference between channels and backplane bus/supply voltage |
Applications
- Relay output control: Controls loads through 4 digital relay outputs with parameterizable output operation.
- Substitute value output: Provides connectable substitute values for the digital outputs.
Key Features
- Relay outputs: 4 parameterizable digital relay outputs support current-sinking and current-sourcing operation.
- Switching voltage: Rated switching voltage is 24 V DC to 120 V DC or 24 V AC to 230 V AC.
- Output current: Maximum current is 5 A per channel and 20 A per module; above +60 °C, continuous current per relay is 3 A.
- Supply and protection: Rated supply voltage is 24 V DC. Reverse polarity protection is provided; external relay-output protection requires a miniature fuse with maximum 6 A tripping current.
- Diagnostics: The module supports diagnostic alarms, supply-voltage monitoring, substitute values, a green PWR LED, a green channel-status LED, and a green/red DIAG LED.
- BaseUnit and connection: The module is usable with BU type B0 or B1; B0 provides 3-wire connection and B1 provides 2-wire connection.
Frequently Asked Questions
1. How many digital outputs does Siemens 6AG2132-6HD01-4BB1 have?
It has 4 digital relay outputs.
2. Which switching voltages are supported?
The rated switching voltage is 24 V DC to 120 V DC or 24 V AC to 230 V AC.
3. What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V DC to 28.8 V DC.
4. Which BaseUnits and connections are supported?
It is usable with BU type B0 or B1. BU type B0 provides 3-wire connection, and BU type B1 provides 2-wire connection.
5. What diagnostics are available?
The module provides diagnostic alarms, supply-voltage monitoring, substitute values, a green PWR LED, a green channel-status LED, and a green/red DIAG LED.