6AG2132-6FD00-4CU0

Siemens 6AG2132-6FD00-4CU0 SIPLUS ET 200SP digital output module with 4 Triac outputs, 230 V AC supply, diagnostics, and BU type U0 connection. Request a model-specific quote.

Product Code
6AG2132-6FD00-4CU0
Dimensions
7.7 × 6.5 × 2.3 cm
Weight
0.059 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type DQ 4×24 … 230 V AC/2 A HF
Digital outputs 4 Triac outputs
Rated output voltage 230 V AC; 24 V AC to 230 V AC
Output current for signal "1" 2 A rated value; 10 mA to 4 A permissible range
Operating modes DQ, DQ with energy-saving function, phase control, half-wave, full-wave
BaseUnit BU type U0
Supply voltage 230 V AC; 47 … 63 Hz
Diagnostics Open-circuit and wire-break detection channel by channel; supply-voltage monitoring; group error
Power loss 9 W typical with 230 V load voltage, all outputs loaded with 2 A, 50 Hz
Protection No short-circuit protection; external fusing necessary
Product lifecycle Active Product

Applications

  1. Digital output control: The module controls digital outputs and can control a digital input.
  2. Phase-control output: The module supports phase control with a control area of 8.5 … 100% of the phase angle.

Key Features

  1. 4 Triac digital outputs: The module has 4 parameterizable, current-sourcing Triac digital outputs with a signal "1" rated output current of 2 A.
  2. AC output range: Output voltage for signal "1" is 20.4 V minimum; the rated output voltage is 230 V AC, with 24 V AC to 230 V AC supported.
  3. DQ and power-control modes: Supported operating modes include DQ, DQ with energy-saving function, phase control, half-wave, and full-wave.
  4. Channel diagnostics: The module provides open-circuit detection channel by channel, wire-break diagnostics channel by channel, supply-voltage monitoring, group error, and diagnostic LEDs.
  5. BU type U0 connection: BU type U0 is used for 1-wire and 2-wire connections; 3-wire connection uses BU type U0 with a Potential distributor module.
  6. SIPLUS environmental design: The module has conformal coating and a -40…+70 °C range, with OT4 and ST1/2 support at +85 °C for 10 minutes.

Frequently Asked Questions

1. How many outputs does Siemens 6AG2132-6FD00-4CU0 have?

It has 4 Triac digital outputs.

2. What output voltage and current does this module support?

The rated output voltage is 230 V AC, with 24 V AC to 230 V AC supported. The signal "1" output current is 2 A rated value, with a permissible range of 10 mA to 4 A; derating data applies in the manual.

3. Which BaseUnit is used for connection?

BU type U0 is used for 1-wire and 2-wire connections. A 3-wire connection uses BU type U0 with a Potential distributor module.

Send Inquiry