Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DQ 4×24 … 230 V AC/2 A HF |
| Digital outputs | 4 Triac outputs |
| Rated output voltage | 230 V AC; 24 V AC to 230 V AC |
| Output current for signal "1" | 2 A rated value; 10 mA to 4 A permissible range |
| Operating modes | DQ, DQ with energy-saving function, phase control, half-wave, full-wave |
| BaseUnit | BU type U0 |
| Supply voltage | 230 V AC; 47 … 63 Hz |
| Diagnostics | Open-circuit and wire-break detection channel by channel; supply-voltage monitoring; group error |
| Power loss | 9 W typical with 230 V load voltage, all outputs loaded with 2 A, 50 Hz |
| Protection | No short-circuit protection; external fusing necessary |
| Product lifecycle | Active Product |
Applications
- Digital output control: The module controls digital outputs and can control a digital input.
- Phase-control output: The module supports phase control with a control area of 8.5 … 100% of the phase angle.
Key Features
- 4 Triac digital outputs: The module has 4 parameterizable, current-sourcing Triac digital outputs with a signal "1" rated output current of 2 A.
- AC output range: Output voltage for signal "1" is 20.4 V minimum; the rated output voltage is 230 V AC, with 24 V AC to 230 V AC supported.
- DQ and power-control modes: Supported operating modes include DQ, DQ with energy-saving function, phase control, half-wave, and full-wave.
- Channel diagnostics: The module provides open-circuit detection channel by channel, wire-break diagnostics channel by channel, supply-voltage monitoring, group error, and diagnostic LEDs.
- BU type U0 connection: BU type U0 is used for 1-wire and 2-wire connections; 3-wire connection uses BU type U0 with a Potential distributor module.
- SIPLUS environmental design: The module has conformal coating and a -40…+70 °C range, with OT4 and ST1/2 support at +85 °C for 10 minutes.
Frequently Asked Questions
1. How many outputs does Siemens 6AG2132-6FD00-4CU0 have?
It has 4 Triac digital outputs.
2. What output voltage and current does this module support?
The rated output voltage is 230 V AC, with 24 V AC to 230 V AC supported. The signal "1" output current is 2 A rated value, with a permissible range of 10 mA to 4 A; derating data applies in the manual.
3. Which BaseUnit is used for connection?
BU type U0 is used for 1-wire and 2-wire connections. A 3-wire connection uses BU type U0 with a Potential distributor module.