Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DQ 16x24VDC/0.5A ST |
| Output type | Source output (PNP, current-sourcing) |
| Digital outputs | 16 |
| Rated output current per channel | 0.5 A |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| BaseUnit | BU type A0 |
| Short-circuit protection | Yes; Electronic |
| Operating temperature | -40…+70 °C; OT4 with ST1/2 (+85 °C for 10 minutes) |
Applications
- Digital output control: Controls digital loads through 16 PNP current-sourcing outputs and can control a digital input.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
Key Features
- Digital outputs: 16 parameterizable source outputs (PNP, current-sourcing), with 0.5 A rated output current per channel.
- Supply and protection: 24 V DC rated supply with a permissible range of 19.2 V to 28.8 V, reverse polarity protection, and electronic short-circuit protection.
- Output switching: Maximum switching capacity is 0.5 A with resistive or inductive load and 5 W with lamp load.
- Diagnostics: Diagnostics monitor supply voltage, wire break, short-circuit to ground, short-circuit to L+, and group error; substitute values are connectable.
- Connection and coding: BU type A0 is used for 1-wire connection; 2-wire and 3-wire connections require BU type A0 with AUX terminals or a potential distributor module. Automatic and Type A mechanical coding are provided.
- Installation and isolation: Maximum module current is 8 A with horizontal installation up to 40 °C or vertical installation up to 30 °C. Isolation is tested with 750 V DC (type test).
Frequently Asked Questions
1. What output type and channel count does 6AG2132-6BH01-4BA0 have?
It has 16 parameterizable source outputs (PNP, current-sourcing).
2. What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC and reverse polarity protection.
3. Which BaseUnit connections are supported?
BU type A0 is used for 1-wire connection. 2-wire and 3-wire connections use BU type A0 with AUX terminals or a potential distributor module.
4. What diagnostics are available?
Diagnostics monitor supply voltage, wire break, short-circuit to ground, short-circuit to L+, and group error. The module also has a green PWR LED, green channel status LED, and green/red DIAG LED.