Technical Summary
| Parameter | Value |
|---|---|
| Digital output type | Source output (PNP, current-sourcing) |
| Digital output channels | 4 |
| Output current per channel | 2 A, rated |
| Supply voltage | 24 V DC rated; 19.2 V to 28.8 V permissible |
| Diagnostics | Supply voltage, wire break, short circuit, group error, diagnostic alarm, and substitute values |
| BaseUnit | BU type A0 |
| Isolation | No isolation between channels; isolated from backplane bus |
| Firmware update | Possible |
Applications
- Digital output control: Controls digital loads through 4 source outputs with a rated output current of 2 A per channel.
- Digital input control: Controls a digital input through the output module.
Key Features
- Digital outputs: 4 parameterizable source outputs (PNP, current-sourcing); current-sinking is not supported.
- Output capacity: Rated output current is 2 A per channel and maximum total current is 8 A per module. With resistive load, switching capacity is maximum 2 A.
- Supply voltage: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics: The module has supply-voltage, wire-break, short-circuit, group-error, diagnostic-alarm, and substitute-value functions. Wire-break and short-circuit diagnoses are module-wise.
- Installation and cable length: Maximum total current depends on installation and temperature: horizontal installation supports 8 A up to 40 °C, 6 A up to 50 °C, 4 A up to 60 °C, and 0.5 A up to 70 °C. Maximum cable length is 1 000 m shielded or 600 m unshielded.
- Isolation and mounting context: The channels are not isolated from each other but are isolated from the backplane bus. The module is usable with BU type A0 and has color code CC02.
Frequently Asked Questions
1. How many digital outputs does Siemens 6AG2132-6BD20-4BA0 have?
It has 4 parameterizable source outputs (PNP, current-sourcing).
2. What supply voltage does this digital output module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V.
3. What diagnostics are available?
It provides supply-voltage, wire-break, short-circuit, group-error, diagnostic-alarm, and substitute-value functions. Wire-break and short-circuit diagnoses are module-wise.
4. Which BaseUnit is usable with this module?
The module is usable with BU type A0.