Technical Summary

Parameter Value
Product type DI 16x24VDC ST
Digital inputs 16
Input voltage, rated value (DC) 24 V
Signal 0 input voltage -30 to +5 V
Signal 1 input voltage +11 to +30V
Parameterizable input delay 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms, plus 30 to 500 μs depending on line length
Rated supply voltage (DC) 24 V
Permissible supply voltage 19.2 V to 28.8 V
Diagnostics Wire break, supply voltage monitoring, diagnostic alarm, group error
Isolation Channels isolated from backplane bus; tested with 750 V DC
BaseUnit connections 1-wire: BU type A0; 2-wire, 3-wire, 4-wire: BU type A0 + Potential distributor module

Applications

  1. Digital signal acquisition: Acquires digital signals through 16 parameterizable 24 VDC inputs.
  2. Input diagnostics: Monitors supply voltage and detects wire breaks, diagnostic conditions, and group errors.

Key Features

  1. Digital input channels: 16 parameterizable digital inputs with a 24 V rated input voltage and IEC 61131 type 3 input characteristic.
  2. Input signal ranges: Signal 0: -30 to +5 V; signal 1: +11 to +30V, with a typical signal-1 input current of 2.5 mA.
  3. Input timing: Parameterizable delay values from 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms, plus a 30 to 500 μs delay depending on line length.
  4. Diagnostics: Module diagnostics include wire-break detection, supply-voltage monitoring, diagnostic alarms, readable diagnostic information, and group error indication.
  5. Supply and isolation: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection. Channels are isolated from the backplane bus and tested with 750 V DC.
  6. Connection and installation: Usable with BU type A0 for 1-wire connection; 2-wire, 3-wire, and 4-wire connections require BU type A0 plus a Potential distributor module. The module is rail-based and has conformal coating.

Frequently Asked Questions

1. How many digital inputs does the 6AG2131-6BH01-4BA0 have?

It has 16 parameterizable digital inputs.

2. What input voltage ranges does this module support?

The rated input voltage is 24 V DC. Signal 0 is -30 to +5 V, and signal 1 is +11 to +30V.

3. What diagnostics are available?

It provides wire-break detection, supply-voltage monitoring, diagnostic alarms, readable diagnostic information, and group error indication. Short-circuit diagnostics are not available.

4. Which BaseUnit is required for the connection variants?

1-wire connection uses BU type A0. 2-wire, 3-wire, and 4-wire connections require BU type A0 plus a Potential distributor module.