Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS ET 200S EM 1 Count 24V/ 100 based on 6ES7138-4DA04-0AB0 |
| Load voltage L+ rated value | 24 V |
| Digital inputs | 1; gate control, synchronization, latch function |
| Digital outputs | 1 |
| Counter input | 1; 32 bit |
| Input voltage ranges | Signal "0": -30 to +5 V; signal "1": +11 to +30V |
| Frequency measurement range | 0.1 Hz to 100 kHz |
| Cycle duration measurement range | 10 μs to 120 s |
| Speed measurement range | 1 1/min to 25 000 1/min |
| Encoder supply output current, max. | 500 mA |
| Output current range | 5 mA to 2 000 mA at 0 to 40 °C; 5 mA to 500 mA at 0 to 60 °C, 1 000 mA at 50 °C |
Applications
- Gate and synchronization input: The digital input supports gate control, synchronization, and latch function.
- Frequency, cycle duration, and speed measurement: The counter supports frequency measurement, cycle duration measurement, and speed measurement across the stated ranges.
- Digital output control: The digital output can control a digital input and switch lamp loads up to 5 W.
Key Features
- Digital I/O and counter: Has 1 digital input with gate control, synchronization, and latch function, plus 1 digital output and 1 counter input with 32-bit resolution.
- 24 V signal ranges: Input voltage is -30 to +5 V for signal "0" and +11 to +30V for signal "1"; output voltage is rated at 24 V.
- Measurement ranges: Measures frequency from 0.1 Hz to 100 kHz, cycle duration from 10 μs to 120 s, and speed from 1 1/min to 25 000 1/min.
- Encoder connections: Connects up to 1 incremental encoder (asymmetrical), 24 V initiator, or 2-wire sensor; encoder supply has short-circuit protection and up to 500 mA output current.
- Diagnostics and protection: Has short-circuit protection, reverse polarity protection for load voltage L+, diagnostic function, and LEDs for group error SF, digital input, digital output, forward counting, and backward counting.
- Installation and environment: Measures 15 mm wide, 81 mm high, and 52 mm deep; module exchange is possible during operation of the IM-DP and under process voltage. Conformal coating is provided for -25…+60 °C.
Frequently Asked Questions
1. How many digital inputs and outputs does 6AG1138-4DA04-2AB0 have?
It has 1 digital input and 1 digital output.
2. What input voltage signals does the module support?
It supports -30 to +5 V for signal "0" and +11 to +30V for signal "1".
3. What frequency range can the counter measure?
The frequency measurement range is 0.1 Hz to 100 kHz.
4. Which encoders can be connected?
The module supports up to 1 incremental encoder (asymmetrical), 24 V initiator, or 2-wire sensor.
5. What is included in the environmental configuration?
It has conformal coating for -25…+60 °C.