6AG1137-6EA00-2BA0

Siemens 6AG1137-6EA00-2BA0 SIPLUS CM CAN module with 1 CAN port, CAN 2.0A/B and CANopen Manager/Slave. Request a model-specific quote.

Product Code
6AG1137-6EA00-2BA0
Dimensions
7.8 × 7 × 2.7 cm
Weight
0.042 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type CM 1x CAN ST
CAN interface 1 port; CAN according to CiA 303-1
CAN operating modes CAN Standard CAN 2.0A/B; CANopen Manager / Slave acc. to CiA
CAN specification CiA 301 & CiA 302
Transmission rate 10 kbit/s to 1 000 kbit/s
Maximum number of devices 60
Supply voltage 24 V DC rated; 19.2 V to 28.8 V DC permissible
Connection Push-in terminal
Isolation 500 V AC or 707 V DC
Address space per module 256 byte maximum

Applications

  1. CAN network gateway: Provides a gateway to CAN Bus or CANopen networks.

Key Features

  1. CAN communication: Gateway to CAN Bus or CANopen networks with CAN Standard CAN 2.0A/B and CANopen Manager / Slave acc. to CiA.
  2. Single CAN port: 1 interface port with CAN according to CiA 303-1 and a push-in terminal connection.
  3. Transmission and device capacity: Transmission rate: 10 kbit/s to 1 000 kbit/s; maximum number of devices: 60.
  4. Supply and isolation: Rated supply voltage: 24 V DC, permissible range: 19.2 V to 28.8 V DC. Reverse polarity protection and isolation are provided; isolation is 500 V AC or 707 V DC.
  5. Diagnostics and services: Diagnostics function, alarms, RUN LED, ERROR LED, green PWR LED, node/life-guarding, Heartbeat, and SYNC are supported.
  6. Installation and dimensions: Dimensions: 15 mm width x 73 mm height x 58 mm depth. Horizontal installation supports -40 °C to 60 °C; vertical, ceiling, and floor installation support -40 °C to 50 °C.

Frequently Asked Questions

1. What CAN operating modes does the 6AG1137-6EA00-2BA0 support?

It supports CAN Standard CAN 2.0A/B and CANopen Manager / Slave acc. to CiA, with CiA 301 & CiA 302 specifications.

2. How many CAN ports and devices does the module support?

It has 1 CAN port and supports a maximum of 60 devices.

3. What CAN transmission rate is supported?

The transmission rate is 10 kbit/s to 1 000 kbit/s.

4. What supply voltage and connection does it use?

The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. The connection is a push-in terminal.